2

ISOM SP005

Response delay t

on

When the value falls below the set response value R

an

, the  ISOM

delays the alarm indication by the response time t

an

 correspond-

ing to the IT system being monitored.
Both the set response delay t

on

 (0...99 s) and the system-related

response time t

an

 delay the alarm indication 

(total delay= t

an

 + t

on

).

If the insulation fault does not continue to exist during the 
response delay, no alarm will be signalled.

Password protection

 (on, OFF)

When password protection has been activated (on), settings can
only be carried out after entering the correct password 
(0...999).

Factory setting FAC

After activating the factory setting, all settings previously
changed are reset to delivery status.

Installation and connection

1.

DIN rail mounting:
Snap the rear mounting clip of the device into place in 
such a way that a safe and tight fit is ensured.
Screw fixing:
Use a tool to move the rear mounting clip (another mount-
ing clip required, see ordering details) into a position that 
it projects beyond the enclosure. Then fix the device using 
two M4 screws.

2.

Connect the device according to the wiring diagram
The connections to KE and E must be led separately!

The front plate cover can be opened by raising the lower part
marked with an arrow.

Ensure safe isolation from supply in the installation
area. Observe the installation rules for live working.

Durée de fermeture t

on

En cas de dépassement d´une valeur de seuil R

an

, le CPI ISOM 

retarde l´émission de l´alarme du temps de réponse t

an

 

correspondant au réseau IT surveillé.
Une durée de fermeture préréglée t

on

 (0...99 s) s´ajoute au temps

de réponse t

an

 et retarde la signalisation (Temporisation totale =

t

an

 + t

on

).

Si le défaut d´isolement ne persiste pas pendant la durée de 
fermeture, l´alarme n´est pas signalée.

Protection par mot de passe

 (on, OFF)

Si le mode de protection par mot de passe a été activé (on), des
saisies ne peuvent être effectuées que si le mot de passe correct
(0...999) a été entré.

Réglage usine FAC

Lorsque les réglages usines sont activés, tous les paramétrages
existant à la livraison sont rétablis.

Installation et branchement

1.

Montage sur rail :
Encliquetez les clips de montage situés au dos de l´appareil 
sur le rail de telle manière que l´appareil soit bien stable.
Fixation par vis :
Utilisez un outil pour amener les clips de montage situés au 
dos de l´appareil (un 2. clip de montage est nécessaire, 
consultez les références) dans une position où ils se 
trouvent au-dessus du boîtier. Fixez ensuite l´appareil au 
moyen de deux vis M4.

2.

Connectez l´appareil selon le schéma de branchement.
Les branchements sur KE et E doivent être effectués 
séparément !

La flèche située à la base du boîtier indique l´endroit où le cache
de la face avant peut être ouvert.

Veillez à l´absence de tension là où se trouve l´instal-
lation et respectez les règles de sécurité en vigueur
pour les travaux sur les installations électriques.

90 mm

45

67,5

36 mm

31,1

47,5

70,5

Accessoires

Содержание 4750 5602

Страница 1: ...nt doit être branché par réseau ou circuit IT Lors de certains contrôles déconnecter les appareils du réseau avant tout essai d isolement ou test diélectrique de l installation Insulation monitoring device Intended use The ISOM SP005 monitors the insulation resistance of deener gized loads These loads e g fire pumps slide valves drives ele vator motors or emergency generators either temporarily de...

Страница 2: ...meture ton En cas de dépassement d une valeur de seuil Ran le CPI ISOM retarde l émission de l alarme du temps de réponse tan correspondant au réseau IT surveillé Une durée de fermeture préréglée ton 0 99 s s ajoute au temps de réponse tan et retarde la signalisation Temporisation totale tan ton Si le défaut d isolement ne persiste pas pendant la durée de fermeture l alarme n est pas signalée Prot...

Страница 3: ...A Gg 11 12 14 Relais d alarme K1 21 22 23 Relais d alarme K2 Relais de défaut du système T R Pour touche Test Reset combinée externe L1 AK Raccord au réseau IT à surveiller Elé ment Fonction Eléments utilisés de l écran Display segments in use Ele ment Function R1 R2 Valeurs de seuil Ran1 Ran2 R1 R2 Response values Ran1 Ran2 1 2 Relais d alarme K1 K2 1 2 Alarm relay K1 K2 t ton Temporisation au dé...

Страница 4: ...tton deleting the fault memory 1 5 s Down key menu items values MENU Démarrage du mode menu 1 5 s Touche Enter 1 5 s points de menu points de sous menu confirmer la valeur 1 5 s Revenir au menu de niveau supérieur MENU Starting the menu mode 1 5 s Enter button 1 5 s MENU Sub menu item con firm value 1 5 s back to the next higher menu level Point de menu Paramètres réglables Structure des menus Men...

Страница 5: ...r at least 1 5 seconds Configurer les paramètres A titre d exemple nous décrivons la modification du seuil d alarme Ran2 R 2 Procédez de la manière suivante 1 Maintenez enfoncée la touche MENU Enter pendant plus de 1 5 s L abréviation AL qui clignote apparaît à l écran 2 Validez avec Enter Le paramètre R1 clignote 3 Appuyez sur la touche fléchée bas pour sélectionner le paramètre R 2 Le paramètre ...

Страница 6: ...tions us ing the UP DOWN keys Configurer les temporisations Déterminez une durée de fermeture ton 0 99 s ainsi qu une temporisation au démarrage t 0 10 s Rétablir le réglage usine et activer désactiver la protection par mot de passe A l aide de ce menu vous pouvez activer ou désactiver la protection par mot de passe ou modifier le mot de passe En outre vous pouvez rétablir les réglages usine sur l...

Страница 7: ... manoeuvres Pour vérifier le branchement correct de l appareil il est conseillé avant la mise en service de l instal lation de contrôler son bon fonctionnement au moyen d une vraie mise à la terre le cas échéant par une résistance RF de valeur adéquate Commissioning Prior to commissioning check proper connection of the ISOM Technical data SP005 Factory setting Insulation coordination acc to IEC 60...

Страница 8: ...ixation rapide sur rail IEC 60715 Fixation par vis 2 x M4 avec clip de montage Poids env approx 150 g Références Type Tension d alimentation Us Réf SP005 DC 9 6 94 V AC 42 460 Hz 16 72 V 4750 5602 SP005 DC 70 300 V AC 42 460 Hz 70 300 V 4750 5723 Tension nominale de réseau Un AGH520S AC 50 400 Hz 0 7200 V 4700 9960 Valeurs absolues du domaine de tension Contact data according IEC 60947 5 1 Rated o...

Страница 9: ...use B P 10 Fax 33 0 3 88 57 78 78 Web http www socomec com 67230 Benfeld France Tous droits réservés Reproduction uniquement avec autorisation de l éditeur Sous réserve de modifications All rights reserved Reprinting and duplicating only with permission of the publisher Subject to change ...

Отзывы: