6- Slot Card Shelf Description & Installation P30112
Print ed in USA – 09/ 11
TO395 Rev. E
Страница 1: ...6 Slot Card Shelf Description Installation P30112 Printed in USA 09 11 TO395 Rev E...
Страница 2: ...1 Station Side Upper Backplane 5 5 2 Station Side Pair Designations 5 5 3 Station Power Ground Connections 6 Figure 2 Station Connectors 6 Figure 3 Connecting 24V External Power Supply 8 Figure 4 Conn...
Страница 3: ...protection from longitudinal voltage surges and Ground Potential Rise GPR that may occur during power system faults 2 2 System Requirements Printed circuit boards designed for installation in the SNC...
Страница 4: ...ber optic isolation cards requires a supply of 24VDC or 48VDC power to operate Floated 48VDC or 130VDC battery and 120VAC power is commonly available at most power substations Various Lyte Lynx intern...
Страница 5: ...ide entrance of card shelf c Strip 1 4 inch from the end of each wire c Secure the wire pairs to the appropriate 18 pin terminal blocks marked ST1 ST2 and ST3 by tightening the screws with a small 1 8...
Страница 6: ...the backplane j acks and assigned a numeric designation i e T1 R1 etc The second pair is connected to the right side of the backplane j acks and is assigned an alpha designation i e TA RA etc See Tabl...
Страница 7: ...RED BLU TC 6 BLU RED RC ST3 51 4 ST3 50 RED ORN T4 7 ORN RED R4 ST3 49 4 ST3 48 RED GRN TD 8 GRN RED RD ST3 47 5 ST3 46 RED BRN T5 9 BRN RED R5 ST3 45 5 ST3 44 RED SLT TE 10 SLT RED RE ST3 43 6 ST3 42...
Страница 8: ...d from the factory with this input terminal wired as primary power 3 BAT Input The third item from the left is a screw terminal block BAT for connecting DC Input Floating Battery 130VDC or 48VDC Only...
Страница 9: ...f as GROUNDED 48VDC A separate wire can be brought into the card shelf and connected directly to the ST1 2 GND and ST2 20 48V terminal block positions The LED indicator j umper J28 must be set to 48V...
Страница 10: ...or power configurations Table 3 Primary Input Voltage Secondary Input Voltage Output Voltage Power Supply Set S5 to Pri Pwr Power Supply Set S5 to Sec Pwr 120 VAC 130 VDC 24 VDC P30114 P30114 48 VDC 2...
Страница 11: ...Side SLOT CONNECTOR COLOR TIP PAIR COLOR RING CONNECTOR J1 RM1 15 WHITE T1 1 BLUE R1 RM1 16 J1 RM1 13 WHITE TA 2 ORANGE RA RM1 14 J2 RM1 11 WHITE T2 3 GREEN R2 RM1 12 J2 RM1 9 WHITE TB 4 BROWN RB RM1...
Страница 12: ...lation equipment shelf and cards and the dedicated entrance cable The 5 kV gap coordinates drainage of surge voltage difference between the dedicated cable pairs and the shield should the power type s...
Страница 13: ...ROUBLE SHOOTING A test card P31102 is recommended for checking correct wiring and correct powering voltages 7 1 LED Not Lit No supply voltage Check with P31102 test card Fuse on AC line receptacle or...
Страница 14: ...GND J1 RM3 RM1 RM2 CTE CTE J3 NOT USED REM GND REM GND T3 R3 J2 REM GND RC TC J3 J4 NOT USED R4 CTE T4 REM GND RD TD CTE J4 J6 J5 REM GND SW1 CTE CTE J6 NOT USED T6 R6 RF TF REM GND R5 CTE T5 REM GND...