Technical Data Sheet FSC-UFC24
Page 8 of 18
November 2017
Technical changes reserved
www.smtec-ag.ch
*Attention: If the FSC-UFC24 is used in combination with the FSC-M200 controller, Modbus
addresses 1-10 are reserved for the FSC-M200. That means that the Modbus addressing of
the FSC-UFC24 starts with Modbus address 11. Furthermore, the Baud Rate needs to be
changed to 38’400 (PIN 5 to ON).
CONF
ON
1 2 3 4 5 6
8
7
If the FSC-UFC24 is used in combination with the FSC-M60, the addressing needs to be done in consecutive
order.
ON
1 2 3 4 5 6
8
7
ADDRESS
Address
Switches On
Address
Switches On
Address
Switches On
Address
Switches On
0*
Broadcast-not in use
33
1+6
66
2+7
99
1+2+6+7
1*
1
34
2+6
67
1+2+7
100
3+6+7
2*
2
35
1+2+6
68
3+7
101
1+3+6+7
3*
1+2
36
3+6
69
1+3+7
102
2+3+6+7
4*
3
37
1+3+6
70
2+3+7
103
1+2+3+6+7
5*
1+3
38
2+3+6
71
1+2+3+7
104
4+6+7
6*
2+3
39
1+2+3+6
72
4+7
105
1+4+6+7
7*
1+2+3
40
4+6
73
1+4+7
106
2+4+6+7
8*
4
41
1+4+6
74
2+4+7
107
1+2+4+6+7
9*
1+4
42
2+4+6
75
1+2+4+7
108
3+4+6+7
10*
2+4
43
1+2+4+6
76
3+4+7
109
1+3+4+6+7
11
1+2+4
44
3+4+6
77
1+3+4+7
110
2+3+4+6+7
12
3+4
45
1+3+4+6
78
2+3+4+7
111
1+2+3+4+6+7
13
1+3+4
46
2+3+4+6
79
1+2+3+4+7
112
5+6+7
14
2+3+4
47
1+2+3+4+6
80
5+7
113
1+5+6+7
15
1+2+3+4
48
5+6
81
1+5+7
114
2+5+6+7
16
5
49
1+5+6
82
2+5+7
115
1+2+5+6+7
17
1+5
50
2+5+6
83
1+2+5+7
116
3+5+6+7
18
2+5
51
1+2+5+6
84
3+5+7
117
1+3+5+6+7
19
1+2+5
52
3+5+6
85
1+3+5+7
118
2+3+5+6+7
20
3+5
53
1+3+5+6
86
2+3+5+7
119
1+2+3+5+6+7
21
1+3+5
54
2+3+5+6
87
1+2+3+5+7
120
4+5+6+7
22
2+3+5
55
1+2+3+5+6
88
4+5+7
121
1+4+5+6+7
23
1+2+3+5
56
4+5+6
89
1+4+5+7
122
2+4+5+6+7
24
4+5
57
1+4+5+6
90
2+4+5+7
123
1+2+4+5+6+7
25
1+4+5
58
2+4+5+6
91
1+2+4+5+7
124
3+4+5+6+7
26
2+4+5
59
1+2+4+5+6
92
3+4+5+7
125
1+3+4+5+6+7
27
1+2+4+5
60
3+4+5+6
93
1+3+4+5+7
126
2+3+4+5+6+7
28
3+4+5
61
1+3+4+5+6
94
2+3+4+5+7
127
Reserved factory
defaults
29
1+3+4+5
62
2+3+4+5+6
95
1+2+3+4+5+7
30
2+3+4+5
63
1+2+3+4+5+6
96
6+7
31
1+2+3+4+5
64
7
97
1+6+7
32
6
65
1+7
98
2+6+7
Modbus and BACnet Addressing