Technical Data Sheet FSC-UFC24

Page 1 of 18 

November 2017  

Technical changes reserved 

www.smtec-ag.ch

Technical Data

Content

Universal Field Controller for motorized fire and smoke extraction dampers.

For bus (Modbus or BACnet) or analog integration into a superior system.

 

Electrical Data

  Nominal Voltage  

24 V AC / DC

 

  Nominal Voltage Range  

-20%... + 20%

 

  Dimensioning  

2 VA + damper actuator (max. 24 VA)

 

  Power Consumption  

2 W + damper actuator

 

  Connections  

AMP plug-in connections and quick 

connections (terminals)

 

Communication / Modbus

  Protocol  

Modbus RTU

 

  Medium  

RS-485, not electrically isolated 

 

  Transmission Formats  

Specified by Modbus RTU Standards

 

  Number of Devices per Line   

100 (without repeater)

 

  Baud Rates  

9’600, 19’200, 38’400, 76’800 bps 

 

  Address  

1..127 (1-10 reserved for FSC-M200) 

(0 reserved for broadcast)

 

  Termination  

120Ω line termination. Jumper 

available on extra pin on PCB. 

Position of jumper if FSC-UFC24 

is last Modbus device in line see 

electrical installation, page 7

 

  Typical Response Time  

<200 ms

Technical Data 

1

Cable Specification 

4

Dimensions 5
Removing the Cover of the Housing 

6

Electrical Installation 

7

Power Supply 

7

Modbus and BACnet Addressing 

8

Configuration through Dip-Switch 

9

Connection Details 

10

Section 

(continuation)

 Page

Section 

(continuation)

 Page

Thermoelectric Tripping Device - Connection 

11

Smoke Detectors – Connections 

12

Analog Application  

13

Electrical Installation for Analog Application 

14

Explanation of LEDs 

15

Functionality of Test Button 

16

Run Time Monitoring of Actuator 

17

Full Auto Test Application 

17

Bus Monitoring Application 

18

Содержание FSC-UFC24

Страница 1: ...r Baud Rates 9 600 19 200 38 400 76 800 bps Address 1 127 1 10 reserved for FSC M200 0 reserved for broadcast Termination 120 line termination Jumper available on extra pin on PCB Position of jumper i...

Страница 2: ...ime 100 ms Device Instant Automatically assigned by physical address writable Safety Protection Class III safety extra low voltage Protection Degree IP42 housing of non flammable polycarbonate Electro...

Страница 3: ...he device contains electrical and electronic components and is not allowed to be disposed of as domestic refuse All locally valid regulations and requirements must be observed Product Features Applica...

Страница 4: ...hrough a digital output signal There is one analog output to signalize the status of the FSC UFC24 and the actuator This analog output can be read from any controller Communication Serial Communicatio...

Страница 5: ...ata Sheet FSC UFC24 Page 5 of 18 November 2017 Technical changes reserved www smtec ag ch 153 mm 57 mm incl bracket 120 mm 116 mm 70 mm 153 mm 130 mm 4 5 mm diameter 100 mm FSC UFC24 Mounting Bracket...

Страница 6: ...cover 2 Unlock the screw which is placed on the lower end in the middle 3 Move the sliding cover 10 mm to the top 4 Remove the cover Lid for Easy Access to Dip Switch Terminals Configuration Addressi...

Страница 7: ...ly Open Position of line termination 120 if FSC UFC24 is last Modbus or BACnet device in line Smoke Detector 24VDC Power supply max 25mA Digital input 24V Can be selected via bus as Normally Open or N...

Страница 8: ...73 1 4 7 106 2 4 6 7 8 4 41 1 4 6 74 2 4 7 107 1 2 4 6 7 9 1 4 42 2 4 6 75 1 2 4 7 108 3 4 6 7 10 2 4 43 1 2 4 6 76 3 4 7 109 1 3 4 6 7 11 1 2 4 44 3 4 6 77 1 3 4 7 110 2 3 4 6 7 12 3 4 45 1 3 4 6 78...

Страница 9: ...of the smoke detector is transferred directly to the system and processed there Smoke Detector Alarm Actuator The signal of the smoke detector is directly linked with the actuator In case of a smoke d...

Страница 10: ...p the power to the actuator is on output open pin nr 1 On power up the CLOSE output will be ON During normal operation the FSC UFC24 in this application ONLY will hold the last command on memory 3 2 1...

Страница 11: ...l AMP plug 2 pole Quick connector 3 pole When a thermoelectric tripping device is mounted in the 2 pole AMP plug the factory production mounted jumper between DI3 and C must be removed The above is on...

Страница 12: ...ct The ORS 142 may only be connected to Hekatron mainspower devices and matches the existing bases type 143 FSC UFC24 24V DC X X X X 6 3 6 5 6 3 6 5 6 3 6 5 24V DC DI2 Com External power supply ABAV S...

Страница 13: ...ipping Device Alarm 10V More than one Alarm Condition During normal operation this output will signalize the position of the damper 2V 4V This output can be connected in parallel between the various F...

Страница 14: ...ontroller with analog input Analog Input Smoke Detector AO 1 Com Analog Ouput Signals the Status of FSC UFC24 0V No Power to FSC UFC24 2V Damper Open 4V Damper Close 6V Smoke Detector Alarm 8V Thermoe...

Страница 15: ...on On Analog connection Error Red Flash Interval 1 sec Actuator did not reach end switch position within the set time Flash Interval 2 sec Smoke detector alarm Flash Interval 3 sec Thermoelectric trip...

Страница 16: ...g test button will interrupt the power supply to the actuator Spring is closing the actuator As soon as the test button is released the power comes back to the actuator and the damper will open again...

Страница 17: ...itch has been reached The timer of the run time monitoring starts to count again as soon as the command open has been sent Once the timer of the set running time has reached the set time the FSC UFC24...

Страница 18: ...1 on Logic Alarm Delay is activated default delay time is 120 sec Option to set the delay time via bus between 30 360 sec Functionality Fire Damper After the defined period of time the fire damper wil...