   INSTRUCTION MANUAL  Release 1  date 05-09-2013 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Fig. 1 : 

Power connection

 

3.3   ADAPTATION CIRCUIT BOARD 

List of conductors to connect to the adaptation circuit board: 

QC1 

Board power supply 
Connect to the point of the safety chain at which the contactor circuit is supplied. 

QC2 

Board power supply common. 
Connect the common of the control voltage feeding the contactor circuit. 

CF1 

Slow Speed Command. 
Connect directly to the low speed contactor, or connect between CF and CF1 a “free 
voltage” normally open contact of the same contactor. 

QU, QUA  

Command for the upward run contactor. 
Interrupt the connection between the up command of the control panel and the coil of the 
upward run contactor. Then connect the wire from the control panel command to terminal 
QU and the coil of the upward run contactor to terminal QUA. 

QD, QDA  

Command for the downward run contactor. 
Interrupt the connection between the down command of the control panel and the coil of the 
downward run contactor. Then connect the wire from the control panel command to terminal 
QD and the coil of the downward run contactor to terminal QDA. 

E-POW 

3  ~ 

 L1  L2  L3 

 U   V  W 

CONTROL 
PANEL 

THREE-PHASE MAINS 

3-POLE + EARTH 

 
CONTACTORS 

CIRCUIT 

INPUT 
CABLE 

OUTPUT 
CABLE 

CONTROL  PANEL  –  MOTOR 
CABLE 