background image

CABLE ENTRY

PIPE ENTRY

HINGED GRILLE

VALVE ACCESS PANEL

FILTER RETAINER

Introduction 
 

This  heater  is  designed  to  be  installed  into  suspended  T-bar  and  plasterboard  ceilings  (The 
minimum height of the void into which the unit will be installed should be a minimum of 250mm). 
 
 

User Information: 

This heater must not be installed in wet rooms or other high humidity areas.  
 
This heater is designed for use on standard two-pipe pumped central heating systems with a 
maximum water temperature of 86° C and a maximum pressure of 6 bar (88lbs/in²). 
Pipe connections are 22mm and either pipe may be used as flow or return.  
 
This heater is classified as a fixed appliance and the electrical connection should be via a 3A fused 
spur. The fused spur must 

not

 be directly below the heater but should be accessible after 

completion of the installation. This heater must be earthed.  
It is recommended that this heater is wired via a remote room thermostat. 
 
To avoid the possibility of vibration this heater must be fitted to a flat even surface. 
 
This heater is fitted with a 35°C Low Limit Stat (L.T.C).  
 
To conform to Building Regulations Part L (Part J in Scotland), a remote room thermostat can be 
used in conjunction with this heater. Refer to the instructions supplied with the thermostat.  

 

Please note the guarantee may be invalidated if this product is not installed and used in 

accordance with these instructions.

 

 

For further details please contact our Technical Support on 01245 324560. 

 

 
 
 
 
 
 
 
 

              

Figure 1 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

Fault Finding 

 
1) 

The fan does not run on any switch setting.

 

a) 

Check the power supply is switched ON. 

b) 

Check the fuse in the fused spur. 

c) 

Check the wiring at the fused spur. 

 
2) 

No heat output. 

a) 

Vent any trapped air from the system (with the heating system turned OFF). 

b) 

Check the central heating is switched ON. 

c) 

If a thermostat is fitted ensure it is calling for heat. 

d) 

Balance the central heating system if installed on the same circuit as panel radiators and 
increase the circulating pump speed if required. 

e) 

Increase the boiler water temperature. 

 
In the event of difficulty please contact our technical help-line on 01245 324560. It will be helpful if 
you do not disconnect the heater from the central heating system. 
 
 

Information and advice 

A product brochure containing full technical specifications and list prices is available to 

download from our website or in hard copy from our office. Also available on our website are 

price lists, individual product datasheets, installation & user guides, where to buy, who to 

contact and a media centre. 

 

Alternatively contact our office 9.00am to 5.00pm Monday to Thursday, 9.00am to 4.00pm  to 

Friday. 

 
 

 

 

Optional Accessories  

 
Optional accessories are available to offer additional control or functionally not offered by the heater 
in its standard configuration.  
 

Electrical Accessories 

Wall Switch Kit                                                                                                            CT60AC WSC 

Allows an on/off wall switch to be mounted on the wall to control heater. 
Suitable cable to connect the switch from the heater to the switch is not supplied. 

Adjustable low temperature cut-out                                                                         CT60 ALTC T3 

This enables the end user to precisely select the temperature at which the fans will switch on when 
combined with different heat sources. 

Miscellaneous Accessories   

Caspian 22mm Flexible Hoses                                                                                          CAS22FH 

Replacement air filters

 

For accessories or spares please contact either your supplier or Smith’s Environmental 
Products Ltd.

 

Содержание CASPIAN SKYLINE CT60 AC

Страница 1: ...nce in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision A means for disconnection from the supply mains having a contact separation in all poles that provides full disconnection under overvoltage category III conditions must be incorporated in the fixed wiring in accordance with...

Страница 2: ...ed appliance and the electrical connection should be via a 3A fused spur The fused spur must not be directly below the heater but should be accessible after completion of the installation This heater must be earthed It is recommended that this heater is wired via a remote room thermostat To avoid the possibility of vibration this heater must be fitted to a flat even surface This heater is fitted w...

Страница 3: ...ounted at a minimum height of 1 8m To the underside of the grille and a maximum height 4m Installation into a suspended T Bar ceiling Figure 3 1 Choose the position in the ceiling grid that the heater is to be installed and remove the chosen ceiling tile as well as any surrounding tiles to provide adequate access during installation 2 Ensure suitable means of support such as threaded rods or chain...

Страница 4: ...eans of support such as threaded rods or chains are used and fixed into place directly above the chosen installation cut out 3 Lift the heater through the cut out into the void and securely attach the supports to the heater 4 Lift the grille into the cut out and adjust the heater so that they meet together 5 Drill four holes 3mm 1 8 holes two in each side and secure with the provided screws see fi...

Страница 5: ...nger should be made using 22mm pipe and fittings Isolating valves should be fitted to ensure the product is serviceable in the future It is advisable to use flexible hoses to reduce vibration available as an accessory see page 7 An air vent must also be fitted to the system pipework above the highest point of the product Pipe entry should be made through the entry holes in the end of the heater sh...

Страница 6: ...ng The heater is fitted with a replaceable air filter To remove the filter lower the hinged grille loosen the two screws securing the filter retainer See Figure 1 slide the across to give access and remove the filter replacing the air filter is the reverse of removing it The filter can be gently tapped or vacuumed to remove any accumulated dust Replacement filters should be fitted as part of regul...

Страница 7: ...nload from our website or in hard copy from our office Also available on our website are price lists individual product datasheets installation user guides where to buy who to contact and a media centre Alternatively contact our office 9 00am to 5 00pm Monday to Thursday 9 00am to 4 00pm to Friday 7 Optional Accessories Optional accessories are available to offer additional control or functionally...

Страница 8: ... instructions It is important to register within 7 days This will ensure you receive a prompt and efficient service if your product requires attention within the guarantee period If you do not register your product you will be required to produce a proof of purchase prior to receiving this service If you experience any problems with the use of your product please contact our after sales office on ...

Страница 9: ...survey the response will help us to serve your needs more effectively Please return by fax to 01245324422 Quality Control Manager Ron Brown ron brown smithsep co uk User Details User Name Mr Mrs Miss Ms Other Initials Surname Address Post Code Telephone Product Model installed e g Space Saver SS5 Room Installed e g Kitchen Your details will only be held by Smiths Environmental Products Ltd and use...

Страница 10: ...s of the nearest approved authorised treatment facility Proper recycling and waste disposal will help conserve resources whilst preventing detrimental effects on our health and the environment WEEE Registered Code WEE ED0093VW In the event of any items missing or visible damage please contact us on 01245 324560 For Ireland Republic Northern contact MT Agencies on 00 353 1 864 3363 In light of our ...

Отзывы: