background image

 

 

PROFILE SERIES 
PSU10, PSU15, PSU23, PSU30 
PSU40 

I

nstallation 

O

perating 

M

aintenance 

 

 

Please read these instructions  thoroughly  before beginning  your installation! 

 

 

The Profile series fan convectors are designed for installation in a forced hot water (hydronic) heating system. 
They may also be used with conventional gas, oil, electric or solar powered water heaters. 

 

IMPORTANT:  BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER 
HEATER, CONSULT YOUR LOCAL PLUMBING CODES. 

 

When installing fan convectors, an accurate heat loss calculation of the space is required.  Match unit selection with 
BTUH output at system water temperature and flow rate.  See the capacity chart below for output at various water 
temperatures and flow rates. 

 

PERFORMANCE & SPECIFICATIONS 

 

Capacities for the Profile fan convectors – BTU/hr @ 65ºF Entering air 
 

Model 

Fan 

Pres.D 

130º 

140º 

150º 

160º 

170º 

180º 

190º 

200º 

210º 

Speed 

rop-ft 

PSU10 

MAX 

2.75 

3307 

4278 

5325 

6192 

7024 

7957 

9081 

9736 

10598 

MIN 

2315 

2994 

3727 

4334 

4915 

5570 

6350 

6810 

7415 

PSU15 

MAX 

3.07 

3983 

5120 

6255 

7382 

8933 

10590 

12250 

14349 

15430 

MIN 

2788 

3580 

4375 

5163 

6250 

7412 

8575 

10040 

10800 

PSU23 

MAX 

3.82 

6645 

8790 

10932 

13070 

15210 

17370 

19500 

21530 

23820 

MIN 

4650 

6150 

7651 

9145 

10645 

12160 

13645 

15072 

16675 

PSU30 

MAX 

4.6 

7550 

10050 

12750 

15800 

19150 

22000 

24900 

27750 

30450 

MIN 

5300 

7030 

8900 

11020 

13380 

15350 

17400 

19425 

21310 

PSU40 

MAX 

4.6 

16500 

19720 

21384 

23166 

25300 

29402 

31600 

35640 

40700 

MIN 

14204 

17000 

18250 

20050 

23008 

25200 

27055 

29184 

31040 

 

 

 

Entering Water Temperature in degrees F – BTU/hr 

 

 

1.  Capacities for the PSU10, 15, 23 are based on 2 gpm.  Correction factors for:  .5 gpm = .80; 1.5 gpm = .96; 2.5 
gpm = 1.07; 3.0 gpm = 1.12 and 5 gpm = 1.23. 

 

2.  Capacities for the PSU30 and PSU40 are based on 3 gpm.  Correction factors for: 1.0 gpm = .85; 5 gpm = 1.18. 

 

Note:  All Smith’s fan  convectors include a low limit aquastat  which shuts  off power to the fan  when water tem- 
perature  falls to 90ºF.  Power is restored when water temperature  rises to 110ºF.   