Instructions for the installer
51
10.2 Adjustment for LPG
Unscrew screw
C
and push air regulator
D
as far
as it will go.
Using a 7-mm wrench, remove nozzle
E
and
replace it with the appropriate nozzle, following the
instructions in the tables for the type of gas to be
used. The nozzle tightening torque must be no
more than
3 Nm
.
Adjust the air by sliding regulator D until distance
“
X
” from the table in “10.4 Primary air adjustment”
is reached.
Lock regulator
D
by tightening screw
C
.
Burner
Rated
heating
capacity
(kW)
LPG – G30/G31
30/37 mbar
Nozzle
diameter
1/100 mm
Reduced
capacity
(W)
Capacity
g/h G30
Capacity
g/h G31
Auxiliary (1)
1.1
48
400
80
79
Semi-rapid (2)
1.7
62
500
124
121
Rapid (3)
3.0
82
1050
218
214
Ultra-rapid (4)
4.2
98
1600
305
300