Instructions for the Installer

9

4)

The regulator must be checked at

a minimum water column of at
least

1”

w.c.

above

the

set

pressure. The inlet pressure to
the regulator should be as follows
for operation and monitoring of
the regulator setting:
-

NATURAL GAS

: Set pressure at

4” water column (101.6 mm).

Supply pressure 3

1

/

2

” - 10

1

/

2

w.c.
-

LP GAS

: Set pressure at 11”

w.c. Supply pressure 8”- 13” w.c.
maximum.

5)

Line pressure testing: Testing above 112 PSI (3.5 kPa), with water column of 14” (35.6 cm) (gauge).

The cooktop and its individual shut-off valve must be disconnected from the gas supply piping system

during any pressure testing of that system at test pressures greater than 1/2 psig (3.5 kPa).

Testing below 112 PSI (3.5 kPa) with a water column of 14” (35.6 cm) (gauge) or lower.
The cooktop must be isolated from the gas supply piping system by closing the respective manual shut-

off valve during any pressure testing of the gas supply piping system at test pressures equal to or less
than 1/2 psig (3.5 kPa).

6)

If the appliance is installed on an oven, the gas pipe must not pass
along the back of the oven, as this may cause overheating.

3.2

Electrical requirements

WARNING

ELECTRICAL SHOCK HAZARD

-

Plug into a grounded 3-prong outlet.

-

Do not cut or remove ground prong.

-

Do not use an adapter.

-

Do not use an extension cord.

-

Failure to follow these instructions can result in death, fire, or electrical
shock.

-

lf codes permit and a separate ground wire is used, it is recommended that a qualified electrician
checks that the ground path is adequate.

-

Check with a qualified electrician if you are not sure whether the cooktop is properly grounded. Do
not ground to a gas pipe.

-

A 120-volt, 60-Hz, AC-only, 15-ampere, fused electrical supply is required. A time-delay fuse or circuit
breaker is recommended. It is recommended that a separate circuit serving only this appliance be
provided.

Содержание PGFU30X

Страница 1: ...Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions lf you cannot reach your gas supplier call the fire department Installation and service must be perfo...

Страница 2: ...nment codes and ordinances WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion or to prevent property damage personal injury or death Do n...

Страница 3: ...Instructions for the Installer 5 2 COOKTOP MEASUREMENTS...

Страница 4: ...ir downward toward the appliance unless the ventilation system and appliance have been designed tested in accordance with ANSI Z21 1 and listed by an independent testing laboratory for combination use...

Страница 5: ...2 50 mm 2 50 mm 2 50 mm 29 15 16 720 mm NOTE 13 330 mm is the maximum recommended upper cabinet depth Gas line opening Wall everywhere 5 12 7 cm below underside of countertop Cabinet base everywhere...

Страница 6: ...to a regular gas supply 1 This installation must conform with all local codes and ordinances In the absence of local codes installation must conform with American National Standard National Fuel Gas...

Страница 7: ...closing the respective manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa 6 If the appliance is installed on an...

Страница 8: ...SI NFPA 70 Electrical Code latest edition or the Canadian Electrical Code CSA and local codes and ordinances lf a mating outlet is not available it is the personal responsibility and obligation of the...

Страница 9: ...CHECK FOR PROPER TIGHTNESS NEVER USE A FLAME Leak testing of the appliance shall be conducted according to the manufacturer s instructions The following procedures must be performed to adjust the gas...

Страница 10: ...o secure the hob to the supporting structure adjusting it until perfectly horizontal Carefully trim off the excess edge of the gasket A pic 2 The dimensions in picture 2 below refer to the distance be...

Страница 11: ...asket B supplied between fitting A adaptator C The adaptor C must be fitted on the gas connection A before fixing the hob Always place a suitable sealing medium such as Teflon tape between pressure re...

Страница 12: ...to the appliance 2 The cooktop s electrical circuit can be checked for proper operation only after top assembly has been completed as and you have checked to ensure that all parts have been fitted pr...

Страница 13: ...quipped with a threee pronge polarized plug grounding which mates with standard three pronged grounding wall receptacles WARNING Label all wires prior to disconnection when servicing controls Wiring e...

Отзывы: