QuickServer Start-Up Guide
Page 18 of 43
7.1 Set IP Address of the QuickServer Using FS-GUI
•
From the FS-GUI main home page, click on setup and then Network Settings
to enter the Edit IP
Address Settings menu.
•
Modify the IP Address (N1 IP Address field) of the QuickServer Ethernet port.
•
If necessary, change the Netmask (N1 Netmask field).
•
Type in a new Subnet Mask.
•
If necessary, change the IP Gateway (Default Gateway field).
•
Type in a new IP Gateway.
NOTE: If the FieldServer is connected to a router, the IP Gateway of the FieldServer should be set
to the same IP Address of the router.
•
Click Update IP Settings, then click on the System Restart to restart the Gateway and activate the
new IP Address.
NOTE: If the FS-GUI was open in a browser, the browser will need to be pointed to the new IP
Address of the QuickServer before the FS-GUI will be accessible again.
NOTE: The SMC Cloud button (see
) allows users to connect to the
SMC Cloud, MSA Safety
’s device cloud solution for IIoT. The SMC Cloud enables secure
remote connection to field devices through a FieldServer and its local applications for
configuration, management, maintenance. For more information about the SMC Cloud,
refer to the
Figure 16: FS-GUI Network Settings