Warning
Caution
Caution
Caution
Manifold Specification
Mounting
When mounting a valve on the manifold base, N.C. and N.O. can
be reversed by a function plate orientation. Also, since cylinder
acts reversely, confirm if the function plate is correctly mounted or
not.
Specifications
Function plate
N.C.
3-CL
N.O.
3-CP
1.
Each valve is fixed to the manifold base with two M4 mounting
screws. Tighten the screws evenly when re-mounting.
2.
For mounting, tighten M4 or equivalent screws evenly into the
mounting holes of the manifold base.
Tightening torque of the mounting screw (M4): 1.4N
・
m
Changing from N.C. to N.O.
If N.O. valve is needed, remove mounting screws of the required
valve and turn over the function plate. (Make sure that there are
gaskets on both sides of the plate.)
Then, tighten the mounting screws to fix the valve to the manifold
base.
∗
This product is delivered as N.C. valve.
Port Direction
1.
For the common exhaust type, pressurization or evacuation of
the R port can cause a malfunction.
2.
In the case of 6 stations or more, supply pressure from both
sides of P port. In the case of common exhaust type, exhaust
air from both sides of R port as well.
Figure: For N.C.
N.O. specifications
N.C. specifications
Function plate
VTA301 Series
Specific Product Precautions 1
Be sure to read before handling.
- 7 -
VT301
∗∗
-OMH0007-B