Series
VQD1000-V
Specific Product Precautions
Be sure to read this before handling.
For Safety Instructions, refer to the back of page 1. For Common Precautions,
refer to “Precautions for Handling Pneumatic Devices” (M-03-E3A).
Connected actuator is started by manual operation.
Use the manual override after confirming that there is
no danger.
Warning
Caution
Non-locking push type (Tool required)
VQD1151W-
(For switching)
10-VQ110-
-X46
(For charging
release air)
Attaching and detaching connectors
To attach a connector, hold the lever and connector unit between
your fingers and insert straight onto the pins of the solenoid valve
so that the lever’s pawl is pushed into the groove and locks.
To detach a connector, remove the pawl from the groove by
pushing the lever downward with your thumb, and pull the
connector straight out.
Note) Gently pull the lead wire, otherwise it may cause contact failure or disconnection.
Caution
VQD1151W-
(For switching)
For the VQD1151W specifications (energy saving type), power
consumption at holding is reduced with the above circuit.
Refer to electrical power waveform as shown below.
<Energy saving type’s electrical power waveform>
(Rated voltage: at 24 VDC)
Caution
When simultaneously energizing 3 stations or more,
make sure to place an energized and non-energized
valve alternatively.
However, if this is not possible and 3 stations or more
need to be energized simultaneously, the energizing
time should be less than 30 minutes to achieve an ener-
gized status not exceeding 50%.
24 V
0 V
3.2 W
2.4 W
0 W
10 to 20 ms
Applied voltage
Cover
Groove
Pin
Lever
Connector
Lever
Connector
ø3
push part
Red
C
Black
A
Lead wire
Connector
Caution
After confirming the gasket is correctly placed under
the valve, securely tighten the bolts with the proper
torque shown in the table below.
• In order to turn it ON, push down the manual
override button in the direction the arrow ( )
indicates until it stops (approx. 0.5 mm), and
release it to turn it OFF.
(+)
(–)
LED
i
1
: Inrush current
i
2
: Holding current
i
1
i
2
Varistor
Manual Override Operation
Valve Mounting
Caution
When piping to a product, check the supply port, etc.
Also, when tightening the piping tube, clamp the base unit to
avoid any undue force from being applied to the valve.
If a force of 120 N or more is applied to the coil especially, the
connecting pin may be deformed, resulting in malfunction.
When Piping to a Product
How to Use Plug Connector
Wiring Specifications
Proper tightening torque (N·m)
0.18 to 0.25
10-VQ110-
-X46
(For charging release air)
Red
C
Black
A
Lead wire
Connector
Coil temperature may get high due to ambient tempera-
ture or energizing duration. Do not touch the valve by
hand directly. When there is such a dangerous case to
be touched by hand directly, install a protective cover.
Warning
Continuous Energization
(+) (–)
(–) (+)
Coil
Coil
Timer circuit
Energy saving type
Back page 2