Series
PPA
Error Correction
Maintenance
When errors occur, they should be corrected as shown below.
Display
Nature of error
Corrective action
Pressure being applied is
above the rating.
Memory data has probably been
corrupted in some way.
Operate within the rated
pressure range.
Perform auto zero
adjustment.
Battery voltage is low.
Replace the batteries.
Entire display
flashes
• Span calibration method
Caution
Caution
Trimmer
Compact
manometer
Compressor
Standard
pressure gauge
Related products useful for line pressure measurement
Valve type
Fluid
Proof pressure
Maximum operating pressure
Operating vacuum pressure
Note 1)
Ambient and fluid temperature
Applicable tubing material
Note 2)
Accessory (option)
2 port valve, 3 port valve
Air
1.5MPa{15.3kgf/cm
2
}
1.0MPa{10.2kgf/cm
2
}
-100kPa{10 Torr}
0 to 60
°
C
Nylon, Soft nylon, Polyeurethane
Bracket
Finger Valve
Series VHK
Specifications
Note 1) For a vacuum application use VHK2 (2 way valve).
Note 2) Use caution with soft nylon and polyeurethane at the maximum operating
pressure. (For further details, refer to catalog CAT.E501-(B), "Fittings &
Tubing for Pneumatic Piping.")
JIS symbols
Tube Coupler
Series KC
Fluid
Maximum operating pressure
Proof pressure
Ambient and fluid temperature
Thread
Thread seal
Adaptor for copper family
incompatible parts
Air
1.0MPa{10.2kgf/cm
2
}
3.0MPa{30.6kgf/cm
2
}
0 to 60
°
C
JIS B0203 (taper thread for piping)
JIS B0211 Class 2 (metric fine screw thread)
With seal (standard equipment)
Part C3604BD (electroless nickel plated)
Specifications
Nylon, Soft nylon, Polyeurethane
ø4, ø6, ø8, ø10, ø12
Mounting
Nut
Body
Stud
Chuck spring
Guide
Collet release bushing
Valve retainer
Stopper
Seal O-ring
C3604BD, PBT
C3604BD (thread)
SUS304
C3604BD, POM
POM
POM
C3604BD, POM
NBR
Principal part materials
These products are convenient for measuring line pressure easily without the need to remove piping or stop supply pressure, etc.
2 port valve
3 port valve
A
I
I
P
R
P
A
5
Do not touch the span calibration trimmer except when performing
span calibration.
1. Perform zero clear at atmospheric pressure.
2. Apply the maximum rated pressure, and calibrate the span while
comparing with a standard pressure gauge.
3. If the display value of the compact manometer is "0" after returning to
atmospheric pressure, then calibration is complete.
If the
display
value is not "0,"
calibrate
again
by
repeating steps
1 and 2.
• Replacing the batteries
When battery voltage becomes low the entire LCD will flash.
When the LCD flashes replace the batteries. Use 2 pcs. of type AA dry
batteries.
To replace the batteries, turn the power OFF and replace them
within approximately 30 seconds.
When not completed within 30 seconds, "Err" will be displayed. In
that case, perform zero clear once again.
In the event that the display runs out of control, remove the batteries for
one minute or longer, and then perform zero clear again after inserting
the batteries and turning on the power.
Tubing material
Tubing outside diameter
Applicable tubing
Pressure can be supplied or stopped by inserting or
removing a tube.
Switching between pressurization and atmospheric
release can be easily performed by switching the control.