(4) Test run
Check the registered positions by operating the electric actuator with
the controller button and switch operation. The test operation
procedure is as follows.
1) Rotate the position switch (h) to the position number to be tested.
2) Confirm that the 7-segment LED (f) flashes at the specified
position number.
3) Press the set button (g).
When the display in LED (f) is changed from flashing state to
no-flashing state, Trial run is completed.
Item
Test operation state
Input of CN4 parallel I/O
Disable
(
Valid only for STOP
)
Output of CN4 parallel I/O
The output state when switching
to manual mode is kept
The display of 7-segment LED
Before Test run
:
The position number flashes
During Test run
:
“-” flashes.
Reaching the target position
:
Position number lit
Adjusting speed and
acceleration
Possible by using (k) to (n)
(5) Setting of Speed and Acceleration
One speed and acceleration can be set for each movement direction (Reverse and Forward) and it is
applied for the operation of all position numbers.
Set the speed and the acceleration by switch (k) to (n) per direction of actuation. The switch can be
set in 16 steps. Actual value depends on the electric actuator. Refer to
“10. Initial setting value of
electric actuator (LEM series)
”
for details of setting the speed and the acceleration. The operation
with the set speed and acceleration can be checked by test run as shown above (4)Test run.
Different speeds and accelerations cannot be individually set for positioning of each position number.
(6) Completion of setting
After set-up is completed, switch to auto mode using the mode switch (e) and perform operation with
PLC. Please confirm
“9. Operation instruction”
for driving instruction method with PLC.
Caution
Close the cover (c) after the switching of the mode to avoid unexpected mode change.
(f) (e) (c)
(g)
(i)
(k)
(m)
(
h)
(j)
(l)
(n)