background image

 

 ITV2-PR-TFM132 

 

Installation and Maintenance Manual 

Electro-Pneumatic Regulator 

(for PROFIBUS DP)  

ITV10*0-PR****-Q,  
ITV20*0-PR****-Q, 
ITV30*0-PR****-Q 

 

1 Safety Instructions 

This manual contains essential information for the protection of users and 
others from possible injury and/or equipment damage. 

• 

Read this manual before using the product, to ensure correct handling, 
and read the manuals of related apparatus before use. 

• 

Keep this manual in a safe place for future reference. 

• 

These instructions indicate the level of potential hazard by label of 
“Caution”, “Warning” or “Danger”, followed by important safety 
information which must be carefully followed. 

• 

To ensure safety of personnel and equipment the safety instructions in 
this manual and the product catalogue must be observed, along with 
other relevant safety practices. 

 

 

 

Caution 

Indicates a hazard with a low level of risk, which if 
not avoided, could result in minor or moderate 
injury. 

 

 

Warning 

Indicates a hazard with a medium level of risk, 
which if not avoided, could result in death or 
serious injury. 

 

 

Danger 

Indicates a hazard with a high level of risk, which if 
not avoided, will result in death or serious injury. 

• 

Electromagnetic compatibility:  

This product is class A equipment intended for use in an industrial 
environment. There may be potential difficulties in ensuring 
electromagnetic compatibility in other environments due to conducted as 
well as radiated disturbances.

 

 

• 

The compatibility of pneumatic equipment is the responsibility of 
the person who designs the pneumatic system or decides its 
specifications

Since the products specified here can be used in various operating 
conditions, their compatibility with the specific pneumatic system must 
be based on specifications or after analysis and/or tests to meet specific 
requirements. 

• 

Only trained personnel should operate pneumatically operated 
machinery and equipment. 

Compressed air can be dangerous if an operator is unfamiliar with it. 
Assembly, handling or repair of pneumatic systems should be performed 
by trained and experienced personnel. 

• 

Do not service machinery/equipment or attempt to remove 
components until safety is confirmed. 

• 

Inspection and maintenance of machinery/equipment should only be 
performed after confirmation of safe locked-out control positions. 

• 

When equipment is to be removed, confirm the safety process as 
mentioned above. Switch off air and electrical supplies and exhaust all 
residual compressed air in the system. 

• 

Before machinery/equipment is re-started, ensure all safety measures 
to prevent sudden movement of cylinders etc. (Supply air into the 
system gradually to create back pressure, i.e. incorporate a soft-start 
valve). 

• 

Do not use this product outside of the specifications. Contact SMC 
if it is to be used in any of the following conditions: 

• 

Conditions and environments beyond the given specifications, or if the 
product is to be used outdoors. 

• 

Installations in conjunction with atomic energy, railway, air navigation, 
vehicles, medical equipment, food and beverage, recreation equipment, 
emergency stop circuits, press applications, or safety equipment. 

• 

An application, which has the possibility of having negative effects on 
people, property, or animals, requiring special safety analysis.  

 

 

• 

Ensure that the air supply system is filtered to 5 microns. 

2 Specifications 

Model 

 

 

ITV*010 

ITV*030 

ITV*050

ITV2090

Min.supply pressure 

(Set pressure) + 0.1 MPa 

(Set pressure) 

–13.3 kPa 

Max.supply pressure 

0.2 MPa 

1.0 MPa 

1.0 MPa

-101 kPa 

Set pressure range 

0.005 ~ 

0.1 MPa 

0.005 ~  

0.5 MPa 

0.005 ~ 

0.9 MPa

-1.3 ~ -80 kPa

Supply voltage 

24 VDC±10% 

Current consumption 

Max. 160 mA 

Input/output data 

12bit/12bit (data 4095 corresponds to 100%F.S.) 

Linearity 

 

 

Max. ±1%F.S.

Hysteresis Max. 0.5%F.S. 

Repeatability 

 

 

Max. ±0.5%F.S.

Sensitivity 

 

 

Max. 0.2%F.S.

Temperature characteristics 

Max. ±0.12%F.S./°C 

Operating temperature 

0~50°C (without condensation) 

Protection structure 

IP65 

 

Model 

 

   

ITV10*0

ITV20*0

ITV30*0

Size (mm) 

50

×

50

×

124 50

×

50

×

146 

66

×

66

×

167

Weight (No option) 

350 g 

450 g 

750 g 

Table 1. 

 
 
 

3 Operation Principle 

When the input signal increases the supply solenoid valve 

n

 turns on and 

the exhaust solenoid valve 

o

 turns off. Supply pressure is passed to the 

pilot valve 

p

 through the supply solenoid valve. The pilot valve will open 

the main valve allowing partial supply pressure to pass to the out port. The 
pressure sensor 

q

 will provide output pressure feedback to the control 

circuit 

r

. The control circuit will balance the input signal and output 

pressure to ensure that the output pressure remains proportional to the 
input signal. 

 
 

 
 
 
 
 
 
 
 
 
 
 

Fig. 1 - Control diagram 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 2 - Schematic diagram 

 
 
 
 
 
 

4 Wiring 

 

Connect the cable to the connector on the main unit as shown in the 
following diagram. Take precautions, as incorrect wiring will damage the 
unit. Use a DC power supply capable of supplying the necessary power 
requirements with minimal ripple. When 3 m straight cable connection is 
specified, this refers to the power supply cable, the communications cable 
should be ordered separately. 
 

Item 

Pin assignment 

Wire colour 

(Note)

1. +24 V 

Brown 

2. N.C. 

– 

3. GND 

Blue 

Connector for 

power supply 

4. N.C. 

– 

1. N.C. 

– 

2. RXD/TXD_N(A) 

Green 

3. N.C. 

– 

4. RXD/TXD_P(B) 

Red 

Connector for 

communication

5. N.C. 

– 

Table 2. 

  

 Note: Wire colour when the optional cable is used. 

 
 

5 LED Display and Communication Protocol 

• LED Display

 

 

 

 

 
 
 
 
 
 

                                                                             

Fig. 3 – Features of the ITV.                       

                                                                                                      

 

 
 

ITEM

LED ON 

LED OFF 

RUN

Power ON (Green) 

Power OFF 

DIA 

Diagnostic error (Red) 

Internal operation is normal 

BF 

Profibus communication error (Red)

Profibus communication is normal 

Table 3. 

• 

Communication Protocol 

Item 

Specification 

Remark 

Communication 
protocol 

PROFIBUS  DP 

For DP-V0 

Baud rate 

(Note)

9.6 k/ 19.2 k/ 45.45 k/  
93.75 k/ 187.5 k/ 500 k/ 1.5 M/ 
3 M/ 6 M/ 12 Mbps 

Set by master 

GSD-File 

 

 

SMC_1412.GSD

Occupied area 
(Input/output data)

1 word / 1 word 

Lower 2 bits of 7 bytes of 
diagnostic area are for diagnostic 
information. 

Communication 
data resolution 

12 bit (4096 resolution) 

 

Address setting 

Switch setting /  
Software setting 

Switching by switch 

Terminator 

Built into the product 

Switching by switch 

Table 4. 

Note: Baud rate relates to communication distance 
 

6 Switch Setting 

• 

Selection of address setting mode    

Node address of the product can be set by 
software mode (SW) or hardware mode (HW). 
When software mode is selected, the  
communication master sets the node address. 
Setting range is 1 to 125.    

 

• 

Address set switch 

In hardware mode use the switches  
shown, to set the node address. 
• Address setting range is 01 to 99. 

 

                                                                        x10                           x1 

6 Switch Setting (continued) 

• 

Setting the terminator                                   

 

 

Set Profibus communication line terminator. 

 

 

 

 

     

 

 

 

     

 

 

 

 

                       With terminator         Without            Without  
                       (factory setting)       terminator        terminator           
 

When the product is connected to the Profibus communication line, 
ensure the switch is set to “with terminator”. 

 

 

• 

Setting the address switch requires the removal of 4 screws in the front 
panel of the unit (Fig 3). Take care as the panel hinges to a maximum of 
90 degrees. 

• 

After setting an address, always close and fix the panel securely. 
Tighten the screws to torque of 0.6 – 0.8 N•m 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

7 Communication Data Allocation 

  Set target value 
  Resolution: 12 bit (100 %F.S.), Occupied byte: 2 Byte 

 

0

0

0

*

  Target value (lower 12 bits) 

 

Target value 
(O area) 

         b15                                                  b11                                                                      b0 

  Put 0 in upper 4 bits 

(Note)

  Monitor the output pressure 
  Resolution: 12 bit (100 %F.S.), Occupied byte: 2 Byte 

 

0

0

0

*

  Output pressure (lower 12 bits) 

 

Output pressure 
(I area) 

         b15                                                  b11                                                                      b0 

  Resolution may exceed 12bit depending on control conditions.
  Monitors the product error. 
  7 bytes are occupied for external diagnostic data. 
  Diagnostic data allocated to byte 7, as shown below. 

Byte7

0

0

0

0

0

0

B

A

 

Diagnostic (DIA) 

            b7                                                                                                         b0 

  A. Internal diagnostic error   0: Normal   1: Error 
  B. Over range error              0: Normal   1: Error 

 

Note: Although 100 %F.S. for target value is 12 bit, communication is 
available upto 150 %F.S. (accuracy is guaranteed upto 100 %F.S.)  
Over range error is output when 150 %F.S. is exceeded.  
Output pressure at this time is controlled by the input data immediately 
before the error occurred. 
Pressure can be set by sending the input data, in which F.S. consists of 
12 bits, to the E/P regulator through the master PLC (target value to 
word area). 

 

Setting data 

0000h 

0FFFh 

[(a/F.S.) x 4095]

HEX

Output pressure 

0 % x F.S. (=0)

100 % x F.S. 

 
 
 
 
 
 
 

 

 

f

 Pressure sensor 

g

 Control circuit 

c

 Supply solenoid valve 

d

 Exhaust solenoid valve

Supply pressure

OUT

– 

Input 
signal 

e

 Pilot valve

3

2

4

5

1

Power supply line 

Communication line

BF LED

RUN LED

Address switch 

DIA LED

OUT

SUP

 
 

   

   

         

 

                

HW/SW 

LED 
indicator 

Power supply 

Control 
circuit 

Input signal 

Exhaust solenoid 
valve 

Supply solenoid 
valve 

Pilot EXH 

Pressure 
sensor 

EXH 

SUP

OUT

Pilot valve 

 

9  0 


9  0 


Отзывы: