background image

 

Wiring and zero point / span adjusting of output 
current of IP

100 type electro-pneumatic positioner 

output signal specification (potentiometer built-in)

 

 
 
This product is IP8100 having potentiometer and the P.C.board built in it. It is for 
ensuring actuator’s opening by 4

20mADC of output signal produced by supplying 

power to it. 
Supplying power can be set freely between DC12

35V. 

 

1.Wiring of input signal , power source and ammeter 

Connect input signal(for positioner control) to 1(+) and 2(

) of the terminal board. 

Connect power source(for detecting output current) to 3(+) and 4(

) of the terminal 

board. 
Connect ammeter in series between (+)side and 3(+) of terminal board or (

)side and 

4(

). 

Please refer Fig.1 for wiring. 

                                                    Fig 1 Wiring diagram 

 
 
 
 
 
 
 
 
 
 
 
 

  NOTE 
    Allowable load resistance in drawing 1 depends on supply voltage 

 
Allowable load resistance is obtained by the formula below. 
    Allowable load resistance 

 (Supply voltage 

 12V) 

 20mADC

  -(1)

 

Normal output current is not be obtained if the load resistance value exceed the result 
of formula(1). Please confirm internal resistance when selecting ammeter. 

 

1

 