HRX-OM-R039
Chapter 9
Product Warranty
Documents
HRSE Series
Product Warranty
8-1
Chapter 8 Documents
8.1 Specifications List
8.1.1
Product specification
Table 8-1 Specifications List [HRSE
-
-10-(T)]
Model
HRSE012-A-10-
(
T
)
HRSE018-A-10-
(
T
)
Cooling method
Air-Cooled refrigerated type
Refrigerant
R407C(HFC)
Quantity of refrigerant
kg
0.3
0.32
Control method
Compressor ON/OFF
Ambient temperature and humidity
1
Temperature: 5 to 35
o
C , Humidity: 30 to 70%
Cir
c
u
la
ti
n
g
f
lu
id
s
y
s
te
m
Circulating fluid
2
Tap water, Ethylene glycol aqueous solution 15%
Operating temperature range
1
o
C
10 to 30
Cooling capacity
(50/60Hz)
W
1000/1200
1400/1600
Temperature stability
4
o
C
±2
Pump capacity
5
(50/60Hz)
MPa
0.08(at 7L/min) / 0.11(at 7L/min)
For option T
:
0.13(at 7L/min) / 0.18(at 7L/min)
Rated fiow
6
(50/60Hz)
L/min
7/7
Tank capacity
L
Approx. 5
Port size
Rc1/2
Wetted material
Stainless steel, Copper brazing (Heat exchanger), Bronze, Brass,
Ceramic, Carbon,
PP, PE, POM, EPDM,PVC
El
e
c
tr
ic
s
y
s
te
m
Power supply
1-phase AC100V 50/60Hz.
Allowable voltage range ±10%
Fuse
A
15
Power supply cable diameter
*10
-
3 cores x 14 AWG (2.0 mm
2
), 3m
Applicable earth leakage breaker
capacity
7
A
15
Rated operating current
3
(50/60Hz)
A
7.1/7.8
For option T : 7.8/8.4
7.1/7.8
For option T : 7.8/8.4
Rated power consumption
3
(50/60Hz)
kVA
0.53/0.54
For option T : 0.62/0.62
0.63/0.63
For option T : 0.72/0.72
Dimensions
8
mm
W377xD435xH615
For option T : W377xD500xH615
Accessory
Fitting (for drain port) 1pc.
Operation manual (Installation
・
Operation (Japanese)) 1pc.
Weight
9
kg
32
For option T : 39
Consult with SMC if using in a season or region where the ambient temperature will fall below zero.
*2 If tap water is used, use water which satisfies the standard of The Japan Refregeration And Air Conditioning Industry Association
(JRA GL-02-1994/Cooling water system - circulation type - make-up water)
*3
(1)Operating ambient temp.: 25
o
C, (2)Circulating fluid temp.: 20
o
C, (3)Circulating fluid rated flow, (4)Criculating fluid : Tap water
The cooling capacity will be reduced by 100W when option T [High head pump] are selected.
*4 Outlet temp. when the circulating fluid flow is rated flow, and the circulating fluid outlet and the return are directly connected.
Installation environment and power supply are within specification range and stable.
*5 The capacity at the thermo-chiller outlet when the circulating fluid temp. is 20
o
C.
*6 Fluid flow to maintain the cooling capacity and the temperature stability.
The specification of the coolong capacity and the temperature stability may not be satisfied if the flow rate is lower than the rated flow.
*7 To be prepared by the customer. Use an earth leakage breaker with sensitivity of 15mA or 30mA/100V in power supply specification
*8 Dimension between panels. Projection is not included.
*9 Weight when the circulating fluid is not included.
*10: Cable is provided with a plug with ground terminal (JIS C8303 Plug for the receptacle with dipole grounding electrodes).