HRX-OM-R039
Chapter 9
Product Warranty
Control, Inspection and Cleaning
HRSE Series
7.3
Consumables
7-5
7.3 Consumables
Replace the following parts depending on their condition.
Table 7-3 Consumables
Part number
Name
Qty.
Remarks
HRS-S0001
Dustproof filter
1
For spare
7.4 Stop for a Long Time
If there is a concern that the product will not be operated for a long period of
time or there is a risk of freezing, conduct the following operations.
1.
T
urn off the user’s power supply.
2.
Drain the circulating fluid of the product completely.
Please refer to
’’7.4.1 Discharge of the circulating fluid’’ for the method of drain the
circulating fluid from the product.
3.
After draining, cover the product with vinyl, etc. and store.
7.4.1
Discharge of the circulating fluid
1.
Place a container underneath the drain outlet.
(The capacity of the container should be approx. 10L.)
Fig 7.4-1
Drain the circulating fluid and facility water from the product
Stop the customer device and release the residual pressure before
discharging the circulating fluid.
Drain port
Container
Clip
Drain plug
Tank lid
Circulating
fluid outlet
Circulating fluid
return port
Normal
Liquid
discharge