Example
// Client Side Connections
Connections
Port
, Baud
, Parity
, Data_Bits
, Stop_Bits
, Protocol
, Poll_Delay
P8
, 2400
, None
, 8
, 1
, SMC2450
, 0.100s
4.3
Client Side Node Descriptors
Section Title
Nodes
Column Title Function
Legal Values
Node_Name
Provide name for node
Up
to
32
alphanumeric
characters
Node_ID
Station address of physical server node
1-129
Protocol
Specify protocol used
SMC2450
Port
Specify which port the device is connected to the
FieldServer
FS-X20: P1
FS-X40: P1
– P8
Example
// Client Side Nodes
Nodes
Node_Name
, Node_ID
, Protocol
, Port
MOD2450
, 1
, SMC2450
, P8
4.4
Client Side Map Descriptor
Section Title
Map_Descriptors
Column Title
Function
Legal Values
Map_Descriptor_Name
Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is
to be stored in the FieldServer
One of the Data Array names from
“Data Array” section above
Data_Array_Offset
Starting location in Data Array
0 to maximum specified in “Data
Array” section above
Function
Function of Client Map Descriptor
RDBC
Node_Name
Name of Node to fetch data from
One of the node names specified in
“Client Node Descriptor” above
Address
Starting address of read block
40001, 30001, etc
Length
Specifies how many register bits
etc. to read
0 - 125
Data_Array_Low_Scale*
Scaling zero in Data Array
-32767 to 32767, 0
Data_Array_High_Scale* Scaling max in Data Array
-32767 to 32767, 100
Node_Low_Scale*
Scaling zero in Connected Node
-32767 to 32767, 0
Node_High_Scale*
Scaling max in Connected Node
-32767 to 32767, 100
Scan_Interval*
Seconds per Scan
0-32000, 1