13-
3.2.1.
MinCycleTime, ProcessDataIn/Out, Device ID
Table 3-3. MinCycleTime, ProcessDataIn/Out, Device ID
Vacuum manifold
stations
MinCycleTime
(Address : 0x02)
ProcessDataIn
(Adress : 0x05)
ProcessDataOut
(Adress : 0x06)
Device ID
(Adress : 0x09...0x0B)
4
0x28 (4.0 ms)
0x83 (4 byte)
0x10 (2 byte)
0x000254
8
0x2E (4.6 ms)
0x84 (5 byte)
0x82 (3 byte)
0x000255
12
0x34 (5.2 ms)
0x85 (6 byte)
0x83 (4 byte)
0x000256
16
0x3A (5.8 ms)
0x86 (7 byte)
0x84 (5 byte)
0x000257
3.3.
IO-Link defined parameters
Table 3-4. IO-Link defined parameters
Index(dec)
Parameter
Access
Value/Description/Remark
0x0002(2) SystemCommand
W
0x0003(3) DataStorageIndex
R/W
---
0x0010(16) VendorName
R
SMC Corporation
0x0011(17) VendorText
R
0x0012(18) ProductName
R
Vacuum manifold 4 stations : EX260-VIL1_4_ejectors
Vacuum manifold 8 stations : EX260-VIL1_8_ejectors
Vacuum manifold 12 stations : EX260-VIL1_12_ejectors
Vacuum manifold 16 stations : EX260-VIL1_16_ejectors
0x0013(19) ProductID
R
EX260-VIL1
0x0014(20) ProductText
R
Vacuum Manifold
0x0015(21) SerialNumber
R
**...*(16 characters max.)
0x0016(22) HardwareRevision
R
V*.*
0x0017(23) FirmwareRevision
R
V*.*.*
0x0018(24) ApplicationSpecificTag
R/W
Default value : **...*(32 characters)
Can be set to 16-32 characters.
0x0024(36) DeviceStatus
R
0x0025(37) DetailedDeviceStatus
R
3.3.1.
SystemCommand (Index 2)
The various reset commands supported by the SI Unit are as follows.
Table 3-5. SystemCommand
Value
Command
Description/Remark
0x80 Device reset
The SI Unit restarts with the power on.
0x81 Application reset
Reset vendor defined parameter to default values while maintaining IO-Link
communication.
0x83 Back-to-box
Reset vendor defined parameter to default values and disable IO-Link
communication.
IO-Link communications can be restored by restarting the SI Unit.