Wiring
Wiring of power supply
The Power supply connection inside the unit has individual power
supplies for solenoid valve actuation (SV power supply) and for
Control parts and Sensor (SW power supply). Supply 24V DC for
each of them. Either single or dual power supply is available. Wiring
is not necessary for SW power supply when no Input Blocks are
used.
Names and Functions of Individual Parts (continued)
PWR(V)
CAN
PWR
ADDRESS
1
0
EX250
CAN
PWR:
Power LED for SI unit
and Input block
PWR(V):
Power LED for
output equipment
SI unit
Input block
Sensor
23V DC
24V DC
Voltage reduction of approx.1V
Power for a sensor is supplied to the sensor connected to an Input
Block. There will be a voltage drop of up to approx. 1V inside the SI
unit, therefore select a sensor which will operate with the resultant
voltage.
If a sensor requires 24V, it is necessary to lower power supply
voltage for sensor slightly or secure a power supply for sensor
separately without going through the SI unit so that sensor input
voltage can be 24V with actual loading (allowable voltage of sensor
power supply: 19.2V to 28.8V).
Power supply connector
Power supply connector M12 male 5pins reverse key type
Communication connector
Communication connector M12 male 5pins
3
2
1
4
5
SW Setting
Address setting
When DIP switch is to be set, turn OFF power supply to SI unit.
LED indication
Node-ID
Setting of Node-ID
Set SW7 to 0. (SW7 is not used.)
Set SW8 to 1.(fixed)
Setting of output when communication stops
SW1
0
0
1
1
2
0
62
0
63
1
SW2
0
0
1
1
1
SW3
0
0
0
1
1
SW4
0
0
0
1
1
SW5
0
0
0
1
1
SW6
0
0
0
1
1
SW9
0
Output V
alue shall take the pre-defined condition specified in
Error V
alue Output Object (6207h,6307h,6327h)
Default: all outputs are cleared.
1
Output V
alue shall be kept.
Output condition of solenoid valve when an error occurs
(Error Control ,Emergency Object) or Fault message is received.
Setting of mode
SW10
1
SW mode. Setting of Node-ID is achieved through net work.
SW1-8 become unavailable. Node-ID can be set up to 127.
Default is 127 (7Fh).
Mode
0
HW mode. Setting of Node-ID is achieved by DIP switches SW1-6.
.
.
.
.
1
0
ON
To enquire about the product, please contact the following:
3
2
1
4
5
Baud rate Table
The CAN LED illuminates RED when an invalid combination is
set with DIP switches SW1-4.
EX250-TFL01GB
(Female connector cable: WAKW4.5T-2 TURCK Co. ,etc.)
(Female connector cable: M12 female 5pins cable with shield
(according to ISO11898))
Green (Flashing) : Pre-Operational State
Green
LED ON
Green
LED OFF
Green
LED ON
Green
LED OFF
Red
LED ON
Green
LED ON
200ms 200ms
Red (Single Flash) : CAN Contoroller Error
OFF
Red
LED ON
Green
LED ON
OFF
200ms 200ms
Green (Single Flash) : Stopped State
200ms
1000ms
1000ms
Red (Double Flash) : Error Control Event
200ms 200ms 200ms
1000ms
Red
LED ON
Green
LED ON
OFF
Green / Red (Flashing) : LSS Configration Mode
LED Indication of SI unit is based on CANopen Specification (CANopen Spec.DR-303-3).
Refer to DR-303-3 Indicator Specification for details.
50ms
50ms
Baud Rate
The baud rate can be set in the HW mode using the following
methods: -
Method of re-setting to default baud rate (125kbps)
1) Turn off the power supply (for CANopen line) and set Node-
ID to 0 with DIP switches SW1-6.
2) The CAN LED will flash RED for five seconds at the
frequency of 2Hz when the power supply to the SI unit is
restored.
3) The baud rate is set to 125kbps and the CAN LED illuminates
green and red alternately (2Hz).
4) Turn off the power supply, set Node-ID, and turn on the
power supply again.
5) The CAN LED illuminates (GREEN). The SI units state of
communication is standby (When SI unit is stand by mode
Pre-operational).
Method of setting baud rate to value within CiA
specification
1) Turn OFF the power supply (for CANopen line) and set
Node-ID to 0 with DIP switches SW1-6.
2) The CAN LED will flash RED for five seconds at the
frequency of 2Hz when the power supply to the SI unit is
restored.
3) Set DIP switch SW6 to 1 while the CAN LED is flashing
(within five seconds).
4) The Flashing CAN LED stops (CAN LED is off). Set the baud
rate with DIP switches SW1-4 within ten seconds according
to the following table.
Wiring
(continued)
Baud Rate (continued)
<Example: If the baud rate of the SI unit is set to 500kbps.>
Because the baud rate is 500kbps, DIP switches SW1-4 setting is 2.
i.e. SW1 = 0 , SW2 = 1 , SW3 = 0 and SW4 = 0
5) The CAN LED flashes RED for two seconds at the frequency
of 1Hz when the setting is successful.
6) After that, the CAN LED flashes RED for five seconds at a
frequency of 5Hz to acknowledge the end of the setting
procedure.
7) The CAN LED illuminates GREEN and RED alternately (at
the frequency of 2Hz).
8) Turn OFF the power supply, set the Node-ID, then turn ON
the power supply again.
9) The CAN LED will illuminate GREEN. The SI units state
ofcommunication is standby (Pre-operational mode).
It is the responsibility of the machine builder to make sure that the
machine operates correctly.
CANopen units from different manufacturers have different ability
(minimum message interval) respectively.
The machine builder should consider the differences in the ability.
The method (confirmed service) of sending the following request after
receiving the response to the request is recommended to ensure correct
communication.
When using the method (unconfirmed service) of sending the following
request without receiving a response to the request, if the request
exceeding the processing performance of the unit is sent, it cannot be
received.
Please confirm the normal operation beforehand when an SMC CANopen
unit is used in your machine.
Please consult with SMC when there is a problem.
Application X
Unconfirmed
service
Application Y, Z, ...
request
indication
indication
indication
Application X
Confirmed
service
Application Y
request
indication
confirmation
response
Indication
Contents
PWR (V)
Green Light ON
When power for solenoid valves and
output equipment is supplied
PWR
Green Light ON
When power for CANopen line, SI unit
and input blocks is supplied
CAN
Green Light ON
When SI unit is in the Operational state
Green Light
(flashing)
SI unit is in the Pre-Operational state
Green Light
(single flash)
Single flash when SI unit is in Stopped
state
Red Light
(single flash)
Single flash when CAN controller error
occurs
Red Light
(double flash)
Double flash when Error Control Event
occurs
Green / Red Light
(flashing)
Flashing when SI unit is in
Configuration mode
(LSS services)
Red Light ON
SI unit is in “Bus OFF” state
DIP switches
SW1-4 setting
0
1
2
3
4
5
6
7
8
Baud rate
(kbps)
1000 800 500 250 125
-
50
20
10
CAUTION
No.
Description
Function
1
SV 24V
+24V for solenoid valve.
2
SV 0V
0V for solenoid valve
3
SW 24V
+24V for sensor input
4
SW 0V
0V for sensor input
5
E
Earth
No.
Description
Function
1
CAN_SHLD
Shield
2
CAN_V+
Power for
CANopen
3
CAN_GND
Power supply - for CANopen
4
CAN_H
CAN_H bus line
(dominant high)
5
CAN_L
CAN_L bus line
(dominant low)
URL http : // www.smcworld.com (Global) http://www.smceu.com (Europe)
AUSTRIA
(43) 2262 62280
NETHERLANDS
(31) 20 531 8888
BELGIUM
(32) 3 355 1464
NORWAY
(47) 67 12 90 20
CZECH REP.
(420) 541 424 611
POLAND
(48) 22 211 9600
DENMARK
(45) 7025 2900
PORTUGAL
(351) 21 471 1880
FINLAND
(358) 207 513513
SLOVAKIA
(421) 2 444 56725
FRANCE
(33) 1 6476 1000
SLOVENIA
(386) 73 885 412
GERMANY
(49) 6103 4020
SPAIN
(34) 945 184 100
GREECE
(30) 210 271 7265
SWEDEN
(46) 8 603 1200
HUNGARY
(36) 23 511 390
SWITZERLAND
(41) 52 396 3131
IRELAND
(353) 1 403 9000
UNITED KINGDOM
(44) 1908 563888
ITALY
(39) 02 92711
Contact
Specifications are subject to change without prior notice from the manufacturer.
The descriptions of products in this document may be used by other companies.
© SMC Corporation All Rights Reserved.