background image

-5- 

 

No.EX

※※

-OMO0007-D 

 

 

NOTE 

○Follow the instructions given below when designing, selecting and handling the product. 

The instructions on design and selection 

(installation, wiring, environment, adjustment, operation, 

maintenance, etc.)

 described below must also be followed.

 

Product specifications 

When conformity to UL is necessary the SI unit must be used with a UL1310 Class2 power supply. 

The SI unit is a UL approved product only if they have a 

  mark on the body. 

Use the specified voltage. 

Otherwise failure or malfunction can result. 

Reserve a space for maintenance. 

Allow sufficient space for maintenance when designing the system. 

Do not remove any nameplates or labels. 

This can lead to incorrect maintenance, or misreading of the operation manual, which could cause damage or 
malfunction to the product. 
It may also result in non-conformity to safety standards. 

 
 

Product handling 

Installation 

Do not drop, hit or apply excessive shock to the fieldbus system. 

Otherwise damage to the product can result, causing malfunction. 

Tighten to the specified tightening torque.

 

If the tightening torque is exceeded the mounting screws may be broken. 

Never mount a product in a location that will be used as a foothold.

 

The product may be damaged if excessive force is applied by stepping or climbing onto it. 

 

Wiring 

Avoid repeatedly bending or stretching the cables, or placing heavy load on them.

 

Repetitive bending stress or tensile stress can cause breakage of the cable. 

Wire correctly. 

Incorrect wiring can break the product. 

Do not perform wiring while the power is on. 

Otherwise damage to the fieldbus system and/or I/O device can result, causing malfunction. 

Do not route wires and cables together with power or high voltage cables. 

Otherwise the fieldbus system and/or I/O device can malfunction due to interference of noise and surge voltage 
from power and high voltage cables to the signal line. 
Route the wires (piping) of the fieldbus system and/or I/O device separately from power or high voltage cables

Confirm proper insulation of wiring. 

Poor insulation (interference from another circuit, poor insulation between terminals, etc.) can lead to excess 
voltage or current being applied to the product, causing damage. 

Take appropriate measures against noise, such as using a noise filter, when the fieldbus system is 

incorporated into equipment. 

Otherwise noise can cause malfunction. 

Содержание EX180-SMJ3 Series

Страница 1: ...No EX OMO0007 D PRODUCT NAME SI unit for CC Link MODEL Series Product Number EX180 SMJ3 5 Series ...

Страница 2: ...y of Product Parts 8 Definition and terminology 8 Installation and Cabling 9 General Instructions on installation 9 Connecting cables 10 LED Display and Settings 12 Troubleshooting and Maintenance 16 Maintenance 20 Specifications 21 Table of specifications 21 Dimensions 22 ...

Страница 3: ... equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced 3 Do not service or attempt to remo...

Страница 4: ...r responsibility a replacement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded from this 1 ...

Страница 5: ...ifications before use Do not operate in an atmosphere containing flammable or explosive gases Fire or an explosion can result This product is not designed to be explosion proof If using the product in an interlocking circuit Provide a double interlocking system for example a mechanical system Check the product regularly for proper operation Otherwise malfunction can result causing an accident The ...

Страница 6: ... is exceeded the mounting screws may be broken Never mount a product in a location that will be used as a foothold The product may be damaged if excessive force is applied by stepping or climbing onto it Wiring Avoid repeatedly bending or stretching the cables or placing heavy load on them Repetitive bending stress or tensile stress can cause breakage of the cable Wire correctly Incorrect wiring c...

Страница 7: ...to sunlight shade the product from the sunlight Otherwise failure or malfunction can result Keep within the specified ambient temperature range Otherwise malfunction can result Do not operate close to a heat source or in a location exposed to radiant heat Otherwise malfunction can result Adjustment and Operation Set the switches by using a sharp pointed screwdriver etc It may damage set switches P...

Страница 8: ... 7 No EX OMO0007 D How to Order EX180 series SI unit Accessories Communication connector Accessories Power supply connector ...

Страница 9: ...itch setting part Set the number of the host stations and the communication speed Definition and terminology Term Explaination N Node number 0 is assigned to the master station of the CC Link network 1 to 64 are assigned to slave stations It is necessary to assign node numbers to slave stations taking into consideration the number of occupied stations so that node numbers are not duplicated Number...

Страница 10: ... catalogues and operation manuals for details on the solenoid valves and manifolds How to mount the manifold 1 Mount the SI unit to the manifold so that the mounting guide of the SI unit case mates with the manifold groove 2 Secure the SI unit using the two sliding locks Caution The EX180 SMJ1 can not mount on the valve manifold for the EX180 SMJ3 5 The EX180 SMJ3 5 also can not mount on the valve...

Страница 11: ...egment as shown in the Figure 2 A cable should be CC Link dedicated one Figure 2 3 The terminating resistance to be connected to the CC Link network depends on the type of cables used Refer to the table below Figure 3 Type of cable Terminating resistor CC Link dedicated cable 110 Ω 1 2 W Built in terminal resistance 110 DIP SW2 No 2 ON CC Link dedicated cable Ver 1 10 CC Link dedicated high perfor...

Страница 12: ...ith another power supply Wire to the assigned pins Figure 5 Figure 6 The tightening torque is 0 22 to 0 25 Nm Note Ground the FG terminal with a ground resistance of 100 Ω or less Tighten the FG terminal M3 round head combination screw firmly with a tightening torque of 0 3 Nm Tighten the connector fixing screws M2 5 slotted head screws firmly with a tightening torque of 0 2 to 0 3 Nm A Dual power...

Страница 13: ...alve power supply is not supplied at specified voltage OFF PWR SI unit power supply supplied within the specified range ON SI unit power supply not connected or out of range OFF L RUN Normal communication ON Communication terminated Time over error OFF L ERR Communication error ON Address or communication speed changed during operation Flashing Normal communication OFF ...

Страница 14: ... 13 No EX OMO0007 D Switch setting Turn off the power supply while setting the DIP switches Open the cover and set the DIP switches with a small flat blade screwdriver ...

Страница 15: ...RY10 RY01 Output No 1 2 E2H RX2F to RX20 162H RY2F to RY20 RY02 Output No 2 E3H RX3F to RX30 163H RY3F to RY30 3 E4H RX4F to RX40 164H RY4F to RY40 E5H RX5F to RX50 165H RY5F to RY50 4 E6H RX6F to RX60 166H RY6F to RY60 RY0D Output No 13 E7H RX7F to RX70 167H RY7F to RY70 RY0E Output No 14 5 E8H RX8F to RX80 168H RY8F to RY80 RX0F RY0F Output No 15 E9H RX9F to RX90 169H RY9F to RY90 RX10 Unused RY...

Страница 16: ...hown in the Figure a If you mount a single solenoid valve on the standard wiring manifold output number for B side valve is skipped Custom wiring for mixed mounting single solenoid valves and double solenoid valves can be specified with a Wiring Specification Sheet Example wiring is shown in the Figure b Bit status 0 and 1 on a data corresponds solenoid valve status ON and OFF 0 OFF 1 ON and outpu...

Страница 17: ...the problem is not found using the troubleshooting provided below it is presumed that the parameter setting of the master station and the network structure are inconsistent In this case please refer to the Troubleshooting section of the CC Link master unit Yes No The solenoid valve does not work correctly Solenoid valve failure Only LED of the solenoid valve is ON Refer to reference No 2 SI unit w...

Страница 18: ...use a broken wire is not applied to the cable Connect the power supply cable correctly Confirm the wiring of the power supply for the solenoid valve is correct Wire correctly Failure of the power supply for the solenoid valve Confirm the supply voltage for the power supply for the solenoid valve Supply 24 VDC 10 5 for the power supply for the solenoid valve 3 L RUN LED is OFF L ERR LED flashes Inc...

Страница 19: ...e Wire correctly Communication failure Check that there is no equipment or high voltage line that can generates noise around the communication and power supply lines Keep the communication and power supply cables away from the noise source Incorrect node number Confirm the node number setting and the station information set in the master station is correct Set correctly Communication speed setting...

Страница 20: ...s noise around the communication and power supply lines Keep the communication and power supply cables away from the noise source 7 Solenoid valve malfunction Solenoid valve failure Check the operation by replacing the solenoid valve Or refer to Troubleshooting for the solenoid valve Check the Troubleshooting for the solenoid valve Or contact to the department in charge of the solenoid valve Conne...

Страница 21: ...r the conductor resistance value Confirm that the resistance value does not exceed the specification If any visible problem is found or the conductor resistance value is out of specification replace the cable Please refer to the specification of the cable for the conductor resistance SI unit No abnormal operation or LED display Replace the SI unit if the operation or LED display is abnormal Power ...

Страница 22: ...t consumption Power supply for SI unit 0 1 A or less Power supply for the solenoid valves Output specification Output type EX180 SMJ3 NPN positive common sink EX180 SMJ5 PNP negative common souce Number of outputs 32 points Connection load Solenoid valve with surge voltage suppressor of 24 VDC and 1 W or less manufactured by SMC Output setting at the time of communication error Hold Clear Switch s...

Страница 23: ... 22 No EX OMO0007 D Dimensions Unit mm EX180 SMJ3 5 EX180 SMJ3A 5A ...

Страница 24: ...ited warranty and Disclaimer are added C Contents are added D Contents are added June 2017 Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 2010 2017 SMC Corporation All Rights Reserved ...

Отзывы: