-79-
No.PF
※※
-OMA1007
■
[F40] Setting for standby/auto isolation function
This is the function to set the parameters for standby mode.
<Operation>
Display [F40] by pressing the UP or DOWN button in function selection mode.
Press the SET button.
Move on to Standby flow rate (Threshold)
Setting of Standby flow rate (Threshold)
Set the value based on the setting method on page
Press the SET button.
Move on to Standby flow rate (Hysteresis)
Setting of Standby flow rate (Hysteresis)
Set the value based on the setting method on page
Press the SET button.
Move on to Standby ON Delay
Setting of Standby ON Delay
Set the value based on the setting method on page
Press the SET button.
Move on to Standby OFF Delay
Setting of Standby OFF Delay
Set the value based on the setting method on page
Press the SET button.
Move on to Auto isolation
Setting of Auto isolation
Select auto isolation OFF or ON with UP or DOWN button.
Auto isolation OFF
Press the SET button
to set.
Return to function
selection mode.
Auto isolation ON
Press the SET button to set.
Move on to auto isolation delay.