2434
SMAY
Sp. z o.o.
17
2434-CPR-0015
PN-EN 12101-8:2012
Smoke control damper
Multi and single compartment
Type: WKP-P
Nominal activation conditions /
sensitivity:
Closure/opening during test at
correct time and in allowable time
Automatic activation - passed
Response delay/closure time:
Automatic activation - passed
Operational reliability:
WKP-P-E-J 300 cycles – pass
WKP-P-E-W 10 000 cycles – pass
Fire resistance:
- Fire integrity – E
- Fire insulation – I
- Smoke leakage – S
- Mechanical stability (under E)
- Maintenance of cross section
(under E)
E
600
120 (v
ed
i<->o) S 1000 C
300
AA single
EI 120 (v
ew
i<->o) S 1000 C
10 000
AA multi
EI 90 (v
ew
i<->o) S 1500 C
10 000
AA multi
Durability
:
- of response delay
- of operational reliability
Pass
Pass