Page
4
of
12
Installation Manual
–
Fire damper KWP-L
Version: 1.6 Date: 25.11.19
Fig.2. Mounting method of fire dampers KWP-L in ceiling
Fig.3.Proposed dimensions of mounting brackets for installation in a ceiling 140 mm thick
Страница 1: ...SMAY Sp z o o ul Ciepłownicza 29 31 587 Kraków tel 48 12 680 20 80 e mail info smay eu www smay eu INSTALLATION MANUAL KWP L FIRE DAMPER SMOKE FIRE ZONE ...
Страница 2: ...ble of Contents 1 INSTALLATION TECHNOLOGY CEILING 3 2 INSTALLATION TECHNOLOGY RIGID WALL 5 3 INSTALLATION TECHNOLOGY STANDARD WALL 7 4 INSTALLATION TECHNOLOGY STRUCTURES THICKER THAN 140 MM 9 5 INSTALLATION TECHNOLOGY MONTAGE AWAY FROM WALL CONSTRUCTION SILICATE BOARDS 10 ...
Страница 3: ...foil or other screening material It can prevent components of fire damper by damage Installation technology Ceiling 1 Make an opening in the ceiling with the dimensions 120 mm greater than the nominal dimensions of the fire damper i e B 120 and H 120 2 Put the closed fire damper into the installation opening and support or suspend in this way that an axis of the fire damper blade matches the axis ...
Страница 4: ...12 Installation Manual Fire damper KWP L Version 1 6 Date 25 11 19 Fig 2 Mounting method of fire dampers KWP L in ceiling Fig 3 Proposed dimensions of mounting brackets for installation in a ceiling 140 mm thick ...
Страница 5: ...e B 120 and H 120 2 Put the closed fire damper into the installation opening and support or suspend in this way that an axis of the fire damper blade matches the axis of the ceiling and ensure a concentricity of fire damper and mounting hole 3 After setting the fire damper as described fill the gap between the fire damper and the wall with cement cement lime mortar or concrete 4 After the mortar h...
Страница 6: ...ation Manual Fire damper KWP L Version 1 6 Date 25 11 19 Fig 5 Installation method of fire dampers KWP L in rigid wall with horizontal rotation axis of damper blade Fig 6 Mounting method of fire dampers KWP L in rigid wall ...
Страница 7: ...e installation opening and support or suspend in this way that an axis of the fire damper blade matches the axis of the ceiling and ensure a concentricity of fire damper and mounting hole 4 After setting the fire damper as described fill the gap between the fire damper and the wall with non flammable mineral wool of high density 100 kg m3 or more 5 Seal the place of filling with mineral wool using...
Страница 8: ...ual Fire damper KWP L Version 1 6 Date 25 11 19 Fig 8 Installation method of fire dampers KWP L in standard wall with horizontal rotation axis of damper blade Fig 9 Mounting method of fire dampers KWP L in standard wall 75 mm thick ...
Страница 9: ...r KWP L Version 1 6 Date 25 11 19 Fig 10 Mounting method of fire dampers KWP L in standard wall 100 mm thick 4 Installation technology Structures thicker than 140 mm Fig 11 Mounting method of fire dampers KWP L in structures thicker than 140 mm ...
Страница 10: ...o bands for a width B 300 mm make four bands For an L 1000 mm distance make an additional four bands b Make individual sections of the promat duct made of PROMATECT L500 panels with a thickness of 50 mm as in the drawing c Suspend the promat duct along with the spacing strips in the spacing L 55 using rails and threaded rods Connect the duct with the wall using PROMAT K84 adhesive d Connect the si...
Страница 11: ... Manual Fire damper KWP L Version 1 6 Date 25 11 19 Fig 12 Montage of fire dampers KWP L away from wall construction according to 2 silicate boards Fig 13 Montage of fire dampers KWP L away from wall construction silicate boards ...
Страница 12: ...Page 12 of 12 Installation Manual Fire damper KWP L Version 1 6 Date 25 11 19 Fig 14 Montage of fire dampers KWP L away from wall construction silicate boards ...