background image

                                                      HMC9000 Diesel Engine Controller User Manual   

HMC9000 Diesel Engine Controller                    2015-12-25                    Version 1.3                Page 9 of 52

 

5  OPERATOR INTERFACE 

5.1 PUSHBUTTONS DESCRIPTION 

 

Stop 

Stop  running  generator  in  local  mode;  During  stopping  process, 

press this button again to stop generator immediately. 

 

Start 

Start genset in local mode. 

 

Remote Mode 

Places  controller  into  its  remote  mode.  In  remote  mode,  engine 

operation can be controlled via remote control module. In local mode, 

except for stop button, all the other panel buttons will be locked. 

 

Local Mode 

Places controller into its local mode. In local mode, controller can be 

started using panel button while remote control will have no effect. 

 

Reset 

If alarm occurs, pressing this button will reset it. All alarm only can 

be removed after reset. 

 

Lamp Test 

Press this button will test panel LED indicators and display screen. 

 

Mute 

Alarm sound off; 

 

Up/Increase 

Screen scroll. 

Up cursor and increase value in setting menu. 

 

Down/Decrease 

Screen scroll. 

Down cursor and increase value in setting menu. 

 

Left 

Screen scroll. 

Left move cursor in setting menu. 

 

Right 

Screen scroll. 

Right move cursor in setting menu. 

 

Set/Confirm 

1.  Pressing and holding for more than 3 seconds enters parameter 

configuration menu;   

2.  In settings menu confirms the set value 

 

Exit 

1.  Returns to the main screen. 

2.  In settings menu returns to the previous screen. 

WARNING:

 Factory default password is 01234. Operator can change the password to prevent others 

from  free  altering  of  the  settings.  Please  clearly  remember  the  password  after  changing.  In  case  of 

password  loss,  please  contact  Smartgen  service  department  enclosing  all  the  information  from  the 

ABOUT

” page of the controller. 

 

 

 

Содержание HMC9000

Страница 1: ...1 HMC9000 DIESEL ENGINE CONTROLLER With J1939 Interface USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO LTD...

Страница 2: ...rt Auxiliary Relay Output 2 7 A Connect to common output port Auxiliary Relay Output 3 7 A Connect to common output port Auxiliary Relay Output 4 7 A Connect to common output port Auxiliary Relay Outp...

Страница 3: ...All alarm only can be removed after reset Lamp Test Press this button will test panel LED indicators and display screen Mute Alarm sound off Up Increase Screen scroll Up cursor and increase value in s...

Страница 4: ...rrent type main battery voltage standby battery voltage charger voltage total running time total start times and GOV output percentage Note sensor names are user set If J1939 is enabled the following...

Страница 5: ...2 Alarm Mute Can prohibit Audible Alarm output when input is active 3 Reset alarm Can reset all alarms when input is active 4 Raise Speed The generator will increase speed by GOV when the input is act...

Страница 6: ...the input is active 23 Water Heating feedback The feedback signal of water heating output The screen displays Water Heating feedback when the input is active 24 Pre lube feedback The feedback signal...

Страница 7: ...mm2 Battery 1 voltage input 4 B1 input 2 5mm2 5 B2 input 2 5mm2 Battery 2 voltage input 6 B2 input 2 5mm2 7 COM Relay 2 5mm2 Common relay power supply input 8 Fuel relay 2 5mm2 DC power is supplied by...

Страница 8: ...ion is fitted Configurable 24 AUX input 4 D 1 0mm2 Digital input Break wire protection function is fitted Configurable 25 AUX input 5 E 1 0mm2 Digital input Break wire protection function is fitted Co...

Страница 9: ...2 Aux input 15 O 1 0mm2 Digital input 53 Aux input 16 P 1 0mm2 Digital input 54 Aux input 17 Q 1 0mm2 Digital input 55 Aux input 18 R 1 0mm2 Digital input 56 COM B input 1 0mm2 57 AIN1 A 1 0mm2 Resist...

Страница 10: ...sion 1 3 Page 42 of 52 11 TYPICAL WIRING DIAGRAM HMC9000 Typical Wiring Diagram Note 1 Power supply for fuel relay start relay and auxiliary outputs 1 5 are supplied by terminal 7 2 To activate batter...

Страница 11: ...if you connect external device with current lower than 0 5A it can be connected directly 2 Controller expansion modules can only be used together with the main controller however the main controller c...

Страница 12: ...he help of PC or DAS Data Acquisition Systems operational software provides a simple and useful marine engine monitoring system management scheme and enables remote control remote measurement and remo...

Страница 13: ...gine 8 pin terminal 4 wire and 5 wire Set auxiliary output 2 as Preheating until cranking and set preheating time as 5 seconds 3 Power supply negative 4 Power supply positive SCR EXPANSION CAN communi...

Страница 14: ...mute and other functions to be performed on the distance All engine parameters and real time events are displayed on the remote control module Note Remote control module can only be used in remote mo...