HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 8 of 69
3
PERFORMANCE AND CHARACTERISTICS
HGM8110DC-2
: It is DC genset controller and used for single automation systems to control genset
start/stop through remote signal control; It is especially suitable for single unit automation system made
up of 1-way DC and 1-way AC.
Main characteristics are as below,
─ 32-bit ARM SCM, highly integrated hardware, reliability gets improved;
─ Vacuum fluorescent display (VFD), selectable Chinese/English interface which can be chosen at the
site, making commissioning convenience for factory personnel;
─ LCD adopts hard screen acrylic material with good wear-resisting and scratch-resisting;
─ Silicone panel and pushbuttons, stronger adaptability of extreme temperature environments;
─ RS485 and RS232 communication interfaces, which can realize ―Three remote functions‖ (remote
control, remote measuring and remote communication) by using MODBUS protocol;
─ ETHERNET communication port, which can realize ETHERNET monitoring method (controller with
ETHERNET port is needed);
─ Equipped with CANBUS port, which can connect ECU engine with J1939, which not only can monitor
frequently-used data (such as water temperature, oil pressure, speed, fuel consumption and so on) of
ECU machine, but also control starting up, shutdown , raising speed and speed droop via CANBUS
port (controller with CANBUS interface is needed);
─ Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems with
voltage 120/240V and system with frequency 50/60Hz;
─ Collects and shows AC 3-phase voltage, current, frequency, power parameters:
─ Collects and shows DC Gen voltage, current, power parameters:
AC
DC
Line voltage (Uab, Ubc, and Uca) voltage U
Phase voltage (Ua, Ub, and Uc) Power
Phase sequence
Current I
Frequency Hz Accumulative Electric Power
Load
Current Ia, Ib, Ic A (unit)
Each phase and total active power P kW (unit)
Each phase and total reactive power Q kvar (unit)
Each phase and total apparent power S kVA (unit)
Each phase and average power factor
λ 1 (unit)
Accumulate total generator power W kWh, kvarh, kVAh (unit)
Earth current I A (unit)
─ For AC Generator, controller has over and under voltage, over and under frequency, over current,
over power, reverse power, loss of phase and reverse phase sequence detection functions; for DC
Generator, controller has over and under voltage, over current, and over power detection functions;
─ 3 fixed analog sensors (temperature, oil pressure and fuel level).
─ 2 configurable analog sensors can be set to sensor of temperature, oil pressure or fuel level;
resistor/voltage/current type sensors are supported;
─ Precisely measure various parameters of engine:
Temp. (WT) °C/°F can be selected
Oil pressure (OP) kPa/psi/bar can be selected