HGM8110DC-2 GENSET CONTROLLER USER MANUAL 

HGM8110DC-2 Genset Controller                    2020-02-20                  Version 1.0                Page 50 of 69 

8.3

 

DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (All Active when connect to 

Ground (B-))   

Table 15 - Defined Contents of Programmable Inputs 

No.   

Type   

Description   

Users Configured 

Including following functions, 

Indication: indicate only, not warning or shutdown.   

Warning: warn only, not shutdown.   

Shutdown: alarm and shutdown immediately   

Trip and stop: alarm, generator unloads and shutdown after 

hi-speed cooling   

Trip: alarm, generator unloads but not shutdown.   

Never: input inactive. 

Always: input is active all the time. 

From crank: detecting as soon as start. 

From safety on: detecting after safety on run delay. 

Reserved 

 

Alarm Mute 

Can prohibit ―Audible Alarm‖ output when input is active.   

Reset Alarm 

Can reset shutdown alarm and trip alarm when input is active.   

60Hz Active 

Use for CANBUS engine and it is 60Hz when input is active.   

Lamp Test 

All LED indicators are illuminated when input is active.     

Panel Lock 

All buttons in panel are inactive except navigation and exit 

buttons and there is 

  on the right of first row in LCD when 

input is active.   

War Mode 

All shutdown alarms except alarms of emergency stop and 

over speed shutdown cannot stop the engine in the war 

mode.   

Idle Mode 

Under voltage/frequency/speed protection is inactive. 

Auto Stop Inhibit 

In 

Auto

 mode, during generator normal running, when input 

is active, inhibit generator shutdown automatically. 

10 

Auto Start Inhibit 

In 

Auto

 mode, inhibit generator start automatically when input 

is active. 

11 

Scheduled Run Inhibit 

In 

Auto

 mode, inhibit scheduled run genset when input is 

active. 

12 

Reserved 

 

13 

Generator Close Status 

Connect generator loading switch‘s Aux. Point.   

14 

Generator Load Inhibit 

Prohibit genset switch on when input is active. 

15 

Reserved 

 

16 

Reserved 

 

17 

Auto Mode Lock 

When input is active, controller enters into auto mode; mode 

selection buttons are inactive. 

18 

Auto Mode Inhibit 

When input is active, controller won‘t work under auto mode. 
Auto mode key and simulate auto key input does not work. 

19 

Reserved 

 

20 

Reserved 

 

Содержание HGM8110DC-1

Страница 1: ...HGM8110DC 2 GENSET CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Страница 2: ...ny material form including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written per...

Страница 3: ...ights an essential element of a procedure to ensure correctness CAUTION Indicates a procedure or practice which if not strictly observed could result in damage or destruction of equipment WARNING Indi...

Страница 4: ...8110DC 2 SWITCH CONTROL PROCEDURES 18 6 PROTECTION 19 6 1 WARNINGS 19 6 2 SHUTDOWN ALARM 22 6 3 TRIP AND STOP ALARM 25 6 4 TRIP ALARM 26 7 WIRINGS CONNECTION 27 8 SCOPES AND DEFINITIONS OF PROGRAMMABL...

Страница 5: ...2 CUMMINS QSL9 60 14 3 CUMMINS QSM11 import 61 14 4 CUMMINS QSX15 CM570 61 14 5 CUMMINS GCS MODBUS 62 14 6 CUMMINS QSM11 62 14 7 CUMMINS QSZ13 62 14 8 DETROIT DIESEL DDEC III IV 63 14 9 DEUTZ EMR2 63...

Страница 6: ...electromagnetic interference Controller is pluggable terminal structure which is very convenient for product maintenance and upgrade and update Controller can display Chinese English and other various...

Страница 7: ...able 3 Models Comparison Models HGM8110DC HGM8110DC 2 Display VFD DC Monitoring Mains Monitoring None None Input Number 8 8 Output Number 8 8 Sensor Number 5 5 Earth Current Schedule Function RS485 ET...

Страница 8: ...on of ECU machine but also control starting up shutdown raising speed and speed droop via CANBUS port controller with CANBUS interface is needed Suitable for 3 phase 4 wire 3 phase 3 wire single phase...

Страница 9: ...pressure generator frequency are optional Wide power supply range DC 8 35 V suitable for different starting battery voltage environment Event log real time clock scheduled start stop generator functi...

Страница 10: ...r Frequency 10 000 Hz max Start Relay Output 16 A DC28V at supply output Fuel Relay Output 16 A DC28V at supply output Programmable Relay Output 1 7A DC28V supply output Programmable Relay Output 2 7A...

Страница 11: ...t 214mm x160mm CT Secondary Current 5A rated Working Conditions Temperature 40 70 C Relative Humidity 20 93 RH Storage Condition Temperature 45 80 C Protection Level IP65 when rubber seal installed be...

Страница 12: ...Manual mode Manual Mode Press this key and put controller in Manual mode Auto Mode Press this key and put controller in Auto mode Alarm Mute Remove alarm sound If there is trip alarm pressing the butt...

Страница 13: ...Default password is 00318 operator can change the password to prevent others changing advanced configurations randomly Please remember the password clearly after change In case that you forget it plea...

Страница 14: ...sor 2 battery voltage charger voltage accumulated run time accumulated start times user A and user B accumulated start times NOTE If engine information are read by J1939 via CAN BUS port then Engine p...

Страница 15: ...an enter parameter settings screen Language Selectable Chinese English and others default Espanol Test Run On load off load and custom commissioning are optional Custom commissioning can be configured...

Страница 16: ...riod low oil pressure high water temperature under speed charge failure alarms are disabled As soon as this delay is over Start Idle Delay is initiated if configured 7 During Start Idle Delay under sp...

Страница 17: ...s into manual mode and its indicator is light on Press to start generator it can automatically detect crank disconnect and generator accelerates to high speed running automatically If high water tempe...

Страница 18: ...tch on transfer failure starts to detect at the same time of close output When detecting time is out if switch on failed it will wait for switch on Otherwise switch on is completed If transfer failure...

Страница 19: ...tects the frequency of AC genset is lower than the set value it will send warn signals 6 AC Over Voltage Active always When controller detects the voltage of AC genset is higher than the set value it...

Страница 20: ...en controller detects the switch on and off fail and the action select enable it will send warn signals 20 DC Over Voltage Active Always When controller detects the voltage of DC genset is higher than...

Страница 21: ...send warn signals 32 Flexible Sensor 1 Low Active from start idle to stop idle When controller detects the sensor value is lower than the min set value it will send warn signals 33 Flexible Sensor 2...

Страница 22: ...he frequency value of AC genset is lower than the set value it will send stop signals 7 AC Over Voltage Active always When controller detects the voltage value of AC genset is higher than the set valu...

Страница 23: ...alue and the reverse power action select shutdown it will send stop signals 20 Temp Sensor Open Active always When controller detects sensor is open circuit and the action select shutdown it will send...

Страница 24: ...detects the sensor value is higher than the max set value it will send stop signals 30 Flexible Sensor 2 Low Active from start idle to stop idle When controller detects the sensor value is lower than...

Страница 25: ...select trip and stop it will send a trip and stop signals 4 AC Over Power Active always When controller detects the over power value of AC genset power is positive is higher than the set value and the...

Страница 26: ...tive always When controller detects the over power value of AC genset power is positive is higher than the set value and the action select trip it will send a trip signals 4 DC Over Current Active alw...

Страница 27: ...ositive of starter battery If wire length is over 30m better to double wires in parallel Max 20A fuse is recommended 3 Emergency stop 2 5mm2 Connected with B via emergency stop button 4 Fuel relay out...

Страница 28: ...nnect Terminal 23 and Terminal 24 at using 24 ECU CAN H 0 5mm2 25 ECU CAN L 0 5mm2 26 CAN2 Internal Resistance Impedance 120 shielding wire is recommended its single end earthed 120 resistor is connec...

Страница 29: ...nstruction 52 Earth Current 1 5mm2 External connected to secondary coil of current transformer rated 5A 53 1 5mm2 54 Aux Input 8 1 0mm2 Ground connected is active B Details see Table 15 55 Aux sensor...

Страница 30: ...as the standard for load power 6 CT Ratio 10 6000 A 20mA 400 Ratio of the external connected DC current transformer 7 Rated Power 10 6000 kW 100 It is rated power for DC generator which is used as the...

Страница 31: ...alarm value and this delay is expired 12 Over Current 0 Disable 1 Enable 1 Alarm is detected after enabled not detected if it is disabled 0 200 110 Set value is DC generator rated voltage s percentag...

Страница 32: ...ng time before genset stop after it unloads 10 Stop Idle Time 0 3600 s 0 Idle running time when genset stop 11 ETS Solenoid Hold 0 3600 s 20 The time of powering up the electromagnet during stop proce...

Страница 33: ...entage of rated speed start alarm handle when it is above this value 0 200 108 Set value is percentage of rated speed when alarm is active and speed is below return value alarm can be cleared automati...

Страница 34: ...enabled not detect alarms when disabled 0 60 0 V 8 0 Set value is percentage of charger voltage During genset normal running process start alarm handle when charger D WL voltage is below this value 0...

Страница 35: ...d and does not enter the normal running period when the generator voltage is less than the load voltage 5 Rated Frequency 10 0 600 0 Hz 50 0 To offer standards for detecting of over under load frequen...

Страница 36: ...er Volt Warn 0 Disable 1 Enable 1 Start to detect alarms when it is enabled not detect alarms when disabled 0 200 110 Set value is percentage of AC Gen rated voltage start alarm handle when it is abov...

Страница 37: ...lay time is expired 16 Loss of Phase 0 1 1 0 Disable 1 Enable 17 Phase Sequence Wrong 0 1 1 AC Load 1 Current Transform 5 6000 A 5A 500 The ratio of external CT 2 Rated Current 5 6000 A 500 Generator...

Страница 38: ...0 200 110 Set value is percentage of AC Gen rated power when power is negative and above this value start alarm handle 0 200 105 Set value is percentage of AC Gen rated power when alarm is active powe...

Страница 39: ...It is detected only after Safety On Delay is over 0 3600 s 3 Alarm starts when temp reaches alarm value and this delay time is expired 4 High Warning 0 Disable 1 Enable 1 Start to detect alarms when...

Страница 40: ...1000 kPa 124 When external oil pressure value is below this value oil pressure low warning alarm is issued It is only detected after Safety On Delay is over 0 1000 kPa 138 When oil pressure low alarm...

Страница 41: ...ontents Setting 0 55 27 Low Oil Pressure Shutdown See Table 15 2 Active Type 0 1 0 0 Closed to Activate 1 Open to Activate Digital Input Port 4 1 Contents Setting 0 55 0 User Configured See Table 15 2...

Страница 42: ...to Activate 1 Open to Activate Digital Input Port 8 1 Contents Setting 0 55 0 User Configured See Table 15 2 Active Type 0 1 0 0 Closed to Activate 1 Open to Activate 3 Arming 0 3 0 0 From safety on...

Страница 43: ...Period 2 3 Custom Period 3 4 Custom Period 4 5 Custom Period 5 6 Custom Period 6 7 Custom Combined 1 8 Custom Combined 2 9 Custom Combined 3 10 Custom Combined 4 11 Custom Combined 5 12 Custom Combin...

Страница 44: ...d wait to stop running time 38 Energise to Stop Used for engines with ETS electromagnet Close when stop idle is over and open when pre set ETS delay is over 39 Speed Drop Pulse Act for 0 1s when contr...

Страница 45: ...when input port 7 is active 76 Digital Input 8 Active Act when input port 8 is active 77 80 Reserved 81 96 Expand Digital Input 1 16 Act when expand input port is active 97 98 Reserved 99 Emergency St...

Страница 46: ...enerator over voltage 127 DC Over Current Act when controller detects DC generator over current 128 DC Over Power Act when controller detects DC generator over power 129 138 Reserved 139 High Temperat...

Страница 47: ...176 Exp1 Ch18 Low Shut 177 Exp1 Ch18 Low Warn 178 Exp1 Ch19 High Shut 179 Exp1 Ch19 High Warn 180 Exp1 Ch19 Low Shut 181 Exp1 Ch19 Low Warn 182 Exp1 Ch20 High Shut 183 Exp1 Ch20 High Warn 184 Exp1 Ch2...

Страница 48: ...02 20 Version 1 0 Page 48 of 69 No Type Description 231 At Manual Mode Act when system is in Manual mode 232 Reserved 233 At Auto Mode Act when system is in Auto mode 234 Generator Load 235 Reserved 2...

Страница 49: ...parts OR condition output S1 or S2 and AND condition output S3 S1 or S2 is TRUE while S3 is TRUE Defined combination output is outputting S1 and S2 are FALSE or S3 is FALSE Defined combination output...

Страница 50: ...indicators are illuminated when input is active 6 Panel Lock All buttons in panel are inactive except navigation and exit buttons and there is on the right of first row in LCD when input is active 7 W...

Страница 51: ...9 Remote Start Off Load In Auto mode when input is active genset can be started automatically and NOT take load after genset normal running when input is inactive genset will stop automatically 30 Man...

Страница 52: ...1 User Configured Resistance 2 User Config 4 20 mA Curve 3 User Config 0 5V Curve 4 VDO 10Bar 5 CURTIS 6 VOLVO EC 7 DATCON 10Bar 8 SGX 9 SGD 10 SGH 11 VDO 5Bar 12 DATCON 5Bar 13 DATCON 7Bar 14 SUSUKI...

Страница 53: ...tor and engine separate as soon as possible b Speed sensor is the magnetic equipment installed on engine body to detect flywheel teeth number c When speed is selected please ensure engine flywheel tee...

Страница 54: ...r minimum set value in case that the condition of too high as well as too low will happen 2 When warning alarms are set please set return value correctly otherwise alarm may not work normally At setti...

Страница 55: ...used sensor user can adjust it in curve type When input the sensor curve X value resistor must be input from small to large otherwise mistake occurs If select sensor type as None sensor curve is not...

Страница 56: ...ng is OK make the start battery power on choose manual mode and controller will execute routine Set controller under manual mode press start button genset will start If start fails after pre set start...

Страница 57: ...ion 1 0 Page 57 of 69 12 TYPICAL APPLICATION Fig 4 HGM8110DC 2 Typical Application Diagram NOTE B fuse minimum 2A and maximum 20A Emergency fuse maximum 32A Customers should select appropriate fuse ba...

Страница 58: ...pply 2 core shielding line The shielding layer should connect to No 16 terminal in controller while another side is hanging in air The other two signal wires are connected to No 17 and No 18 terminals...

Страница 59: ...is load current transformer s secondary side is prohibited to have open circuit 13 6 WITHSTAND VOLTAGE TEST CAUTION When controller has been installed in control window if it needs voltage withstand t...

Страница 60: ...communication shielding line connect with ECU terminal only CAN H SAE J1939 signal Impedance 120 connecting line is recommended CAN L SAE J1939 return Impedance 120 connecting line is recommended Engi...

Страница 61: ...C CAN communication shielding line connect with ECU terminal only CAN H A Using impedance 120 connecting line CAN L B Using impedance 120 connecting line Engine type Cummins ISB 14 4 CUMMINS QSX15 CM5...

Страница 62: ...SX Modbus 14 6 CUMMINS QSM11 Table 29 Engine OEM Connector Terminals of controller OEM connector of engine Remark Fuel relay output 38 Start relay output Connect with starter coil directly CAN GND CAN...

Страница 63: ...TZ EMR2 Table 32 F Connector Terminals of controller F connector Remark Fuel relay output Expand 30A relay battery voltage of 14 is supplied by relay Fuse is 16A Start relay output Connect to starter...

Страница 64: ...tput X1 34 X1 Terminal 33 connected to negative of battery Table 36 ADEC X4 Connector Terminals of controller SMART X4 port Remark CAN GND X4 3 CAN communication shielding line connect to controller s...

Страница 65: ...ctor Remark Fuel relay output 3 Start relay output Connect to starter coil directly CAN GND CAN communication shielding line connect with controller s terminal only CAN H 9 Using impedance 120 connect...

Страница 66: ...CAN H 12 Using impedance 120 connecting line CAN L 13 Using impedance 120 connecting line Engine type VolvoEDC4 14 18 VOLVO EMS2 Volvo Engine types are TAD734 TAD940 TAD941 TAD1640 TAD1641 and TAD1642...

Страница 67: ...20 connecting line Table 46 Engine 2 Pin Connector Battery Engine 2 pins Remark Battery negative 1 Wire diameter 2 5mm2 Battery positive 2 Wire diameter 2 5mm2 Engine type BOSCH 14 20 WEICHAI It is su...

Страница 68: ...able or via switchboard The communication between the controller and monitoring equipment is carried out by using TCP ModBus protocol NOTE In this connection mode controller parameters can be set Smar...

Страница 69: ...Check programmable inputs Crank not disconnect Check fuel oil circuit and its connections Check starting batteries Check speed sensor and its connections Refer to engine manual Starter no response Che...

Отзывы: