![Smartgen HGM6100N-RM Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/smartgen/hgm6100n-rm/hgm6100n-rm_user-manual_1297462011.webp)
HGM6100N-RM REMOTE MONITORING MODULE USER MANUAL
HGM6100N-RM Remote Monitoring Module 2019-08-06 Version 1.0 Page 11 of 14
No.
Function
Cable Size
Description
13
14
Charger (D+)
1.0mm
2
15
Speed Sensor Input
0.5mm
2
16
Speed
Sensor
Input;
connected battery negative
inside controller already
17
Engine Temp.
1.0mm
2
18
Oil Pressure
1.0mm
2
19
Fuel Level
1.0mm
2
20
Aux. Input 1
1.0mm
2
21
Aux. Input 2
1.0mm
2
22
Aux. Input 3
1.0mm
2
23
IA
1.5mm
2
24
IB
1.5mm
2
25
IC
1.5mm
2
26
ICOM
1.5mm
2
27
U
1.0mm
2
28
V
1.0mm
2
29
W
1.0mm
2
30
N2
1.0mm
2
31
R
1.0mm
2
32
S
1.0mm
2
33
T
1.0mm
2
34
N1
1.0mm
2
35
RS485 SCR
/
Impedance
120
Ω
shielding
wire
is
recommended;
single
end
is
ground
connected.
36
RS485-
0.5mm
2
37
RS485+
0.5mm
2
38
Aux. Input 4
1.0mm
2
NOTE
: HGM6100N-RM doesn't have the functions.
39
Aux. Input 5
1.0mm
2
40
Sensor COM
1.0mm
2
41
CAN SCR
0.5mm
2
42
CAN L
0.5mm
2
43
CAN H
0.5mm
2
44
NULL
NOTE:
Back panel USB is parameter programming port, and controller can be configured via PC.
NOTE:
Configured parameters of HGM6100N-RM shall be in accordance with that in the monitored HGM6100N