HFC6100LT Fan Controller User Manual Page 14 of 24
No.
Item
Range
Default
Remark
17
Return
Difference
Value of Sensor 2
(0-300)
℃
5
During the fan output control process,
temperature difference required when the
fan output is turned off.
18
Sensor
3
Curve
Selection
(0-15)
10
PT100, refer to Table 8.
19
Sensor 3 Open Circuit
(0-1)
0
0: Inactive 1: Alarm
20
Sensor 3 High Alarm
Threshold Value
(0-300)
℃
95
When the temperature of external temp.
sensor is higher than this value, it will
send high temperature signal. When the
setting value is equal to 300, it will not
send the signal.
21
Sensor 3 Control Fan
Groups
(0-5)
3
3 groups of fan controlled.
22
Sensor
3
Custom
Curve
Custom temperature sensor curve (X: Resistance Y:
Temperature).
23
Sensor 3 Fan Control
Curve
Custom fan control curve (X: Temperature Y: Number of fan
output)
24
Return
Difference
Value of Sensor 3
(0-300)
℃
5
During the fan output control process,
temperature difference required when the
fan output is turned off.
25
Sensor
4
Curve
Selection
(0-15)
10
PT100, refer to Table 8.
26
Sensor 4 Open Circuit
(0-1)
0
0: Inactive 1: Alarm
27
Sensor 4 High Alarm
Threshold Value
(0-300)
℃
95
When the temperature of external temp.
sensor is higher than this value, it will
send high temperature signal. When the
setting value is equal to 300, it will not
send the signal.
28
Sensor 4 Control Fan
Groups
(0-5)
4
4 groups of fan controlled.
29
Sensor
4
Custom
Curve
Custom temperature sensor curve (X: Resistance Y:
Temperature).
30
Sensor 4 Fan Control
Curve
Custom fan control curve (X: Temperature Y: Number of fan
output)
31
Return
Difference
Value of Sensor 4
(0-300)
℃
5
During the fan output control process,
temperature difference required when the
fan output is turned off.
32
Sensor
5
Curve
Selection
(0-15)
10
PT100, refer to Table 8.
33
Sensor 5 Open Circuit
(0-1)
0
0: Inactive 1: Alarm
34
Sensor 5 High Alarm
Threshold Value
(0-300)
℃
95
When the temperature of external temp.
sensor is higher than this value, it will
send high temperature signal. When the
setting value is equal to 300, it will not
send the signal.