HAT828 High Speed ATS Controller User Manual Page 6 of 56
2
PERFORMANCE AND CHARACTERISTICS
——
Can complete power outage detection and control signal output within 15ms after power off;
with high speed PC two-stage switch, it can realize switching within power outage 20ms;
——
Suitable for PC two-stage transfer switch (normal and high speed);
——
System type can set as: Mains-Gen, Gen-Mains, Mains-Mains, Gen-Gen;
——
4.3-inch single color 240x128 LCD display with white backlight, multilingual interface
(Simplified Chinese, English, other), other is default as Traditional Chinese, push-button
operation;
——
Collect and display 2-way 3-phase voltage, frequency and phase sequence;
——
Synchronous transfer when power is available on both sides (including abnormal situation);
——
Display accumulated close times, auto transfer times, mains failure transfer times;
——
Display current continuous supply time and S1/S2 accumulated supply time, auto transfer
running time;
——
With over/under voltage, over/under frequency, loss of phase, reverse phase sequence
detection function;
——
Auto/Manual mode transfer. In manual mode, it can manually control switch transfer;
——
All parameters can be configured on site. Passwords authentication ensures authorized
staff operation only;
——
Manual commissioning on site to achieve genset start/stop operation;
——
With switch re-closing function;
——
Closing output signal can be set as pulse or continuous output;
——
2-way N-wire isolated design;
——
Real-time clock (RTC); event log function (event log can record 200 items circularly);
——
With black box function, can record 5 groups of events in ATS auto transfer circularly, 60
detailed data of 50s before each event record, and 10s after each event record;
——
Scheduled routing run & scheduled not run (can be set as start genset once a
day/week/month whether with load or not);
——
Can control two gensets to work as cycle run mode, master run mode and balanced run
mode;
——
With customized boot screen function;
——
Widely DC power supply range allows the controller can bear instantaneous DC 80V input;
——
AC power supply can be phase voltage (L-N) or line voltage (L-L), supply range
AC(90~576)V;
——
Large terminal space allows the controller can bear maximum AC 625V voltage input;
——
With Dual-RS485 isolated communication interface. With “four remote” (remote control,
remote measurement, remote communication, remote adjusting) function by the
ModBus-RTU communication protocol. Genset start/stop and switch transfer can be