HAT600R Series ATS Controller User Manual Page 31 of 59
No.
Item
Description
21
Forced Manual Mode
Forcibly set controller mode as manual mode.
22
Forced Auto Mode
Forcibly set controller mode as manual mode.
23
Panel Lock
Panel button operation is prohibited;
Up/Down/Set/Return/Alarm Reset can be used;
24
Sync Inhibit
Sync transfer function is inactive;
25
Scheduler Inhibit
Scheduled start and scheduled not start functions are inactive;
26
Simulate S1 OK
Simulate S1 power is normal; S1 voltage detection is inactive;
27
Simulate S2 OK
Simulate S2 power is normal; S2 voltage detection is inactive;
28
Open IN
Same as panel open key, used to control switch open, please use
auto reset button.
29
Reserved
30
Auto Trans./Restore
After this port is configured, it is Auto Trans./Restore when it is
active; it is Auto Trans./Non Restore when it is inactive.
31
Switch Output Voltage
Abnormal Fault
After this port is configured, fault alarm occurs when it is active.
(HVD100 voltage detection module as signal input is needed.)
32
Switch Output Voltage
Abnormal Warn
After this port is configured, warning alarm occurs when it is active.
(HVD100 voltage detection module as signal input is needed.)
33
Remote Control Inhibit
When it is active, all remote control commands by communication
port are inactive.
34
Transition Inhibit
In Auto mode, after this signal is active, it can inhibit ATS to
transfer.
35
Busbar
Voltage
Abnormal
After this port is configured, warning alarm occurs when it is active.
36
Reserved
37
Reserved
38
Reserved
39
Reserved