HAT600P Series ATS Controller User Manual Page 8 of 58
3
PERFORMANCE AND CHARACTERISTICS
—
LCD 132x64 pixel with backlight, multiple language display (Simplified Chinese, English, Other),
push button operation;
—
LED lamp can directly display current ATS close/open status, power status and whether load is
power on;
—
System type can be set to: Mains (1#) & Mains (2#), Mains (1#) & Generator (2#), Generator (1#) &
Mains (2#), Generator (1#) & Generator (2#);
—
S1 master, or S2 master can be set; Auto Transfer Auto Recover and Auto Transfer Non Recover
are fitted for master power;
—
Measure and display 2-way 3 phase Voltage, Frequency, and Phase Sequence Status;
—
Collect and display load active power, reactive power, apparent power, power factor and current;
—
Independent overcurrent warning or trip alarm functions for S1/S2;
—
NEL trip function is fitted;
—
Load voltage monitoring function is fitted;
—
Display of accumulated active power, accumulated reactive power, accumulated close times is
fitted;
—
Each phase voltage of S1/S2, wave distortion rate of load current and 3-21 odd times harmonic
percentage can be measured;
—
Display of current power supply time and S1/S2 continuous power supply time is available;
—
Automatic and manual synchronous transfer function is applicable, and the difference of voltage,
frequency and phase of two circuits can be displayed;
—
For energy saving switch, users can wait for and close the switch until PF (close is ready) signal is
active;
—
Over/under voltage, over/under frequency, loss of phase, reverse phase sequence monitoring
functions are fitted;
—
Auto/Manual transfer is fitted, so that breaker can be forced to close or open in manual mode;
—
With local mode, the controller only displays data parameter when it is active and the switch needs
to be transferred by external operations;
—
Electrical interlock release function for switching in parallel (HAT600PS only)
—
Has an in-place mode. When this mode is valid, the controller only displays data parameters, and
the switch needs to be converted by external operations
—
All parameters can be configured on site; password is used to verify in case of non professionals
wrong operation;
—
Custom start screen function is fitted;
—
Commissioning can be done manually on site to conduct genset start/stop operations;
—
Switch re-close and breakout re-close functions are fitted;
—
Close output can be set to pulse or continuous output;
—
Applicable for switches of PC class two segments, PC class three segments, CB class and CC
class;
—
2 circuit N wire isolated design;
—
Real time clock display, and event log function, which can record 200 data circularly;
—
Black box function, which can record 5 sets of events of ATS transfer, and 60 detailed data of 50s
before one set occurs and 10s after the event;
—
Scheduled run/not run function for genset, run for once, run monthly or weekly, and run on load or
unload can also be set;
—
Two gensets can be controlled and cycle run, master run, and balanced time run can be realized.
—
Wide DC supply range, maximum 80V DC input for transient;
—
Wide wire terminal space of AC input, maximum 625V voltage input;
—
USB port, provides convenience for on-site debugging, and parameter or software upgrade;
—
RS485 isolated communication port, makes the controller has remote control, remote
communication, remote measuring, remote debugging functions by ModBus-RTU; it can remote
control genset start/stop, ATS close and open;
—
ETHERNET port, makes the controller has remote control, remote communication, remote