HAT600P Series ATS Controller User Manual Page 33 of 58
9.4
DIGITAL OUTPUT PORT FUNCTION DESCRIPTION
Table 20 Output Port Function Description
No.
Items
Description
0
Not Used
Output port is inactive.
1
Custom Combined 1
2
Custom Combined 2
3
Custom Combined 3
4
Custom Combined 4
5
Custom Combined 5
6
Custom Combined 6
7
Reserved
8
Reserved
9
Reserved
10
Reserved
11
Common Alarm
It includes fault alarm and warning alarm.
12
Common Fault Alarm
It includes “Transition Fault” alarm, and “Over Current” trip
alarm.
13
Common Warn Alarm
It includes reverse phase sequence of S1, reverse phase
sequence of S2, load over current and forced open.
14
Transition Fault
It includes “S1 Fail to Close” alarm, “S1 Fail to Open” alarm,
“S2 Fail to Close” alarm, “S2 Fail to Open” alarm.
15
Audible Alarm
It can be connected with annunciator externally when
common alarm is active. When “alarm mute” input is active
or 60s delay has expired, it can remove the alarm.
16
Reserved
17
Genset Start Delay
Output when genset start delay is initiated;
18
Genset Stop Delay
Output when genset stop delay is initiated;
19
Elevator Control
Output before load is power off or switch transfer; used to
control running elevator to stop at the nearest level until
transfer is finished;
20
Fire Control Linkage
Output when forced to open (Fire) input signal is active and
ATS succeeds to open.
21
Busbar Voltage Abnormal
Output
Output when busbar voltage abnormal warning input is
active.
22
Reserved
23
S1 Available
Output when S1 voltage is normal.
24
S1 Unavailable
Output when S1 voltage is abnormal.
25
S2 Available
Output when S2 voltage is normal.
26
S2 Unavailable
Output when S2 voltage is abnormal.
27
S1 Over Current
Output when S1 is over current with load;
28
S2 Over Current
Output when S2 is over current with load;
29
Local Mode
Output when the local mode is active.
30
Auto Mode
Output when the genset is in Auto mode.
31
Manual Mode
Output when the genset is in Manual mode.
32
Genset Start Output
Control the genset starting.
33
Reserved
34
S1 Close Control
Control the S1 switch to close.
35
S1 Open Control
Control the S1 switch to open.
36
S2 Close Control
Control the S2 switch to close.
37
S2 Open Control
Control the S2 switch to open.
38
Reserved
39
Reserved
40
NEL1 Trip Control
Control NEL unload when output is active; used to control
NEL unload and return (on load) when output is inactive;
41
NEL2 Trip Control