![Smartgen HAT163 Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/smartgen/hat163/hat163_user-manual_1297480010.webp)
HAT163 ATS CONTROLLER USER MANUAL
HAT163 ATS Controller 2018-05-20 Version 1.0 Page 10 of 21
7. DEFINITION AND RANGE OF PARAMETERS
Table 6
– Parameters Definition and Range Table (1)
No.
Items
Range
Default
Description
1 AC System
(1-4)
1
1: 3 Phase, 4 Wire (3P4W)
2: Single Phase, 2 Wire (1P2W)
3: 3 Phase, 3 Wire (3P3W) (special order required)
4: 2 Phase, 3 Wire (2P3W)
2 S1 Normal Delay
(1-7)
2
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined(Default: 5s)
3 S2 Normal Delay
(1-7)
2
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined(Default: 5s)
4
S1 Abnormal Delay
(1-7)
2
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined(Default: 5s)
5 S2 Abnormal Delay
(1-7)
2
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined(Default: 5s)
6 Close Delay
(1-7)
4
1: Continuous Close Enabled
2: 1s
3: 3s
4: 5s
5: 8s
6: 10s
7: User defined(Default: 5s)
7 Open Delay
(1-7)
3
1: 1s
2: 3s
3: 5s
4: 8s
5: 10s
6: 15s
7: User defined(Default: 5s)