CMM366A-ET Cloud Monitoring Communication Module User Manual
CMM366-ET Cloud Monitoring Communication Module 2017-12-21 Version 1.0 Page 6 of 15
4 PANEL AND TERMINAL DESCRIPTION
4.1
PANEL INDICATOR AND BUTTONS
Fig.1 - CMM366A-ET Front Panel Diagram
Table 3
– Indicators Description
Icon
Note
POWER/ALARM
GreenLED Light: Power supply normal indicator
RedLED Light: Common alarm indicator
RS485(Red)
Normally Extinguish: RS485 disabled
Normally Light: Communication fail
Blink: Communication normal
USB(Red)
Normally Extinguish: USB(Host) disabled
Normally Light: Communication fail
Blink: Communication normal
ETHERNET(Red)
Normally Extinguish: CMM366A-ET login with server unsuccessfully
Normally Light: Login with server successfully
Blink: Real-time communication normal
LINK(Red)
Normally Extinguish: Disabled
Normally Light: Communication fail
Blink: Communication normal
RS232(Red)
Normally Extinguish: RS232 disabled
Normally Light: Communication fail
Blink: Communication normal
Lamp test/Reset:
Press this button for 1s, all the LEDs are illuminated; press for 10s, reset the module to default and all
the LEDs blink for 3 times.
NOTE: After reset the module, parameters need to re-configured via PC software. Please operate
cautiously.