Smartgen CMM366A-3G Скачать руководство пользователя страница 4

                       

CMM366A-3G Cloud Monitoring Communication Module User Manual 

CMM366A-3G Cloud Monitoring Communication Module          2017-12-23        Version 1.0      Page 4 of 17

 

1  OVERVIEW 

CMM366A-3G

 Cloud Monitoring Communication Module is GPRS wireless network communication 

protocol switch module which can achieve genset (with SCI) connect to Internet. After logging into cloud 

server, module will receive corresponding genset controller communication protocol from cloud server. 

And the module gains genset data via RS485 port, USB port, LINK port or RS232 port. Then the module 

transmits  the  data  to  corresponding  cloud  server  via  GPRS  wireless  network 

for  achieving  user’s 

real-time monitoring to running status and searching of running records via APP (IOS or Android) and 

PC terminal devices. 

CMM366A-3G

 module not only can achieve genset monitoring but also can insert some digital alarm 

input/output signal to achieve monitoring of generator room entrance guard, guard against theft and fire 

facilities. 

CMM366A-3G

  module,  which  has  GPS  locate  function,  can  upload  gained  longitude,  latitude  and 

elevation to corresponding cloud server. 

2  PERFORMANCE AND CHARACTERISTICS 

 

Connect to cloud server via WCDMA 3G&GPRS 2G, one to one monitoring; 

 

Multiple  ports  for  communication  with  genset  control  module:  RS485,  RS232,  LINK  and  USB 

(Host); can monitor great majority genset control modules of international first-class brands; 

 

Widely power supply: DC (8~35)V, can direct use genset build-in battery; 

 

With ARM-based 32-bit SCM, high integration of hardware and strong programming ability; 

 

Include with GPS locate function to achieve location information and locate genset; 

 

Take  JSON  network  data  communication  protocol,  upload  real-time  data  variation  and  take 

compression algorithm to vastly reduce network flow at the same time; 

 

When alarm occurs it can upload data to server immediately; 

 

2 auxiliary digital input ports which can receive external alarm signal; 

 

1 auxiliary relay output ports which can output various of alarm signal; 

 

Power and multiple communication status indicators on front panel that working status is clear at a 

glance; 

 

Lamp test function; 

 

Parameter adjust function: users can adjust parameters via USB port; 

 

Take standard 

π-type 35mm guide-rail installation or screw-fixed installation that the module can 

be installed in the genset control box; 

 

Modular  design,  self  extinguishing  ABS  plastic  shell,  light  weight,  compact  structure  with  easy 

installation. 

 

 

 

 

 

 

 

Содержание CMM366A-3G

Страница 1: ...CMM366A 3G CLOUD MONITORING COMMUNICATION MODULE USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD ...

Страница 2: ...material form including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above Any reference to trademarked product names used within this publication is owned by their...

Страница 3: ...CIFICATION 5 4 PANEL AND TERMINAL DESCRIPTION 6 4 1 PANEL INDICATOR AND BUTTONS 6 4 2 GPRS 7 4 3 GPS 7 4 4 SIM INSTALLATION 7 4 5 RS485 8 4 6 RS232 8 4 7 LINK 8 4 8 USB HOST 9 4 9 USB DEVICE 9 4 10 TERMINAL 10 5 PROGRAMMABLE PARAMETERS 11 5 1 CONTENTS AND SCOPES OF PARAMETERS 11 5 2 PC CONFIGURATION INTERFACE 13 6 SYSTEM DIAGRAM 14 7 CASE DIMENSION AND INSTALLATION 15 8 TROUBLESHOOTING 16 9 PACKIN...

Страница 4: ...RFORMANCE AND CHARACTERISTICS Connect to cloud server via WCDMA 3G GPRS 2G one to one monitoring Multiple ports for communication with genset control module RS485 RS232 LINK and USB Host can monitor great majority genset control modules of international first class brands Widely power supply DC 8 35 V can direct use genset build in battery With ARM based 32 bit SCM high integration of hardware and...

Страница 5: ...al Input connect B is active Auxiliary Output 1A DC30V Volts free output USB Host A type USB female port RS485 Isolated type RS232 General type LINK SmartGen exclusive port USB Device B type USB female port GPRS Port Standard SMA port female SMA port male for antenna GPS Port Standard SMA port female SMA port male for antenna active antenna Wireless Network WCDMA 3G GPRS 2G Case Dimensions 72 5mmx...

Страница 6: ...Communication normal GPS Red Normally Extinguish GPS disabled Normally Light GPS not gained satellite signal Blink GPS gained satellite signal LINK Red Normally Extinguish Disabled Normally Light Communication fail Blink Communication normal RS232 Red Normally Extinguish RS232 disabled Normally Light Communication fail Blink Communication normal GPRS 3G Red Extinguish CMM366A 3G login with server ...

Страница 7: ...curate or cannot be gained Antenna 50Ω SMA female active antenna Figure 1 CMM366A 3G Antenna Connection NOTE GPRS antenna and GPS antenna cannot be connected reversely 4 4 SIM INSTALLATION Insert 3G or 2G SIM card CMM366A 3G will connect to servers via GPRS network NOTE WCDMA 3G network all 2G network are supported Use standard SIM card 25mmX15mm GPS indicator and GPRS indicator blink in the same ...

Страница 8: ...RS485 port If communication is abnormal 120Ω terminal resistance is recommonded One end of shield wire hangs in the air and the other one connects with SCR Figure 3 RS485 Connection 4 6 RS232 Receive genset data information by connecting module RS232 port with Genset Controller RS232 port Figure 4 RS232 Connection 4 7 LINK Receive genset data information by connecting module LINK port with Genset ...

Страница 9: ...Page 9 of 17 4 8 USB HOST Receive genset data information by connecting module USB port with Genset Controller USB port via USB cable Figure 6 USB HOST Connection 4 9 USB DEVICE All the parameters can be configured and view CMM366A 3G ID Login password by connecting USB port with USB disk of PC software Figure 7 USB Connect PC Device ...

Страница 10: ...battery 2 B 1 0mm2 Connected with positive of starter battery 3A fuse is recommended 3 Aux Input 1 1 0mm2 Active when connect to B 4 Aux Input 2 1 0mm2 Active when connect to B 5 Aux Output Normally Open 1 0mm2 Volt free output with 1A DC30V 6 Common 1 0mm2 7 Normally Close 1 0mm2 8 RS485 B 0 5mm2 Impedance 120Ω shielding wire is recommended its single end earthed 9 RS485 A 0 5mm2 10 RS485 SCR 0 5...

Страница 11: ...0 4 Altitude 9999 9 9999 9 m 100 0 GSM 1 GSM Enabled 0 1 1 0 Disabled 1 Enabled 2 GPRS Password Reserved 3 SMS Center Number Reserved 4 PIN Enabled 0 1 0 0 Disabled 1 Enabled 5 APN 0 65535 40 characters Input Port Input 1 1 Setting 0 9 0 Default Not used 2 Type 0 1 0 0 Close to Activate 1 Open to Activate See Table 6 Digital Input Ports Content 3 Delay 0 20 0 0 0 Action delay Input 2 1 Setting 0 9...

Страница 12: ...eserved 7 Reserved 8 Reserved 9 Factory Test Mode It is only used for factory hardware port test when active Table 7 Relay Output Ports Content No Item Description 0 Not used Output port won t output when this item is selected 1 Digital Input 1 Active Output when auxiliary input 1 is active 2 Digital Input 2 Active Output when auxiliary input 2 is active 3 RS485 Communication Failure Output when R...

Страница 13: ...oud Monitoring Communication Module 2017 12 23 Version 1 0 Page 13 of 17 5 2 PC CONFIGURATION INTERFACE Connecting the USB port of CMM366A 3G communication module with PC USB port to configure the parameters Figure 8 Gateway Configuration Figure 9 Module Monitoring Interface ...

Страница 14: ... 3G Cloud Monitoring Communication Module 2017 12 23 Version 1 0 Page 14 of 17 6 SYSTEM DIAGRAM One CMM366A 3G module connects with one genset monitor module It can be connected via RS485 port LINK port RS232 port or USB port Figure 10 CMM366A System Application Diagram ...

Страница 15: ...ommunication Module 2017 12 23 Version 1 0 Page 15 of 17 7 CASE DIMENSION AND INSTALLATION 2 ways for installation 35mm guide rail in box or screw M4 installation as below Figure 11 CMM366A 3G Case Dimension Figure 12 CMM366A 3G Guide Rail Installation Figure 13 CMM366A 3G Screw Installation ...

Страница 16: ...ot Gained Location Check GPS parameters are enabled or not Check GPS antenna is connected or not and placed outdoor or not RS485 Communication Abnormal Check connections Check RS485 port is enabled or not Check settings of genset ID and baud rate are correct or not Check RS485 s connections of A and B is reverse connect or not RS232 Communication Abnormal Check connections Check RS232 port is enab...

Страница 17: ...oring Communication Module 2017 12 23 Version 1 0 Page 17 of 17 9 PACKING LIST Table 9 Packing List No Name Quantity Remark 1 CMM366A 3G 1 2 Osculum type GSM antenna 1 3 External GPS antenna 1 4 120Ωmatched resistor 2 5 Certification 1 6 User manual 1 _________________________________ ...