6 OPERATION
Fig. 4 BAC2410BST MASK
Table 3 Connection Description
Terminal
Function
Description
L
AC Terminals
Connect terminals L and N to AC voltage (100~240)V by
using greater than BVR 1.5mm
2
multi-strand copper line.
N
PE
GND Terminals
Connect to shell internally already.
BOOST
Mode Selection
3-stage: BOOST and B- are short circuited;
2-stage: BOOST is hung up.
B-
Battery Negative
Connect to battery negative by using greater than BVR
2.5mm
2
multi-strand copper lines.
B+
Battery Positive
Connect to battery positive by using greater than BVR
2.5mm
2
multi-strand copper lines.
FULL
CHARGRD
Green LED Indicator
Fully charged indicator
CHARGING
Red LED Indicator
Charging indicator
NOTES:
1)
Because there is diode and current-limiting circuit inner the charger, it can be used together with charging generator,
and there is no need to disconnect the charger when cranking;
2) When this is applied on genset, as charging current is very big, there shall be voltage decreasing on the charging wire.
Therefore it is recommended to connect charging wire with battery terminals separately for avoiding disturbance on
sample precision.