NB40F3UX – NB40S2UX – NB40LP2UX - NB40LPS2UX
REV 01 – Dec. 2019 - ENGLISH
LED will flash rapidly. At the second alarm event within this
period, the green LED will flash for 1 second to simulate
smoke delivery.
Remember to activate the normal operating mode
(DIP SW7 OFF) at the end of the test.
TEST CAPSULE (
NCBT
)
The test capsule (NBCT) is an accessory that allows you
to test the operation of the device in operating mode. It
simulates the behavior of the smoke capsule, but instead
of delivering the smoke it emits a series of beeps and turns
on its LEDs. NUBI 4.0 with the test capsule is immediately
operational and ignores the 30 minute safety time
described below.
COMMISSIONING
We recommend carrying out a test (see the previous
chapter Testing mode) before carrying out a final
commissioning of the device. Set DIP SW7 to OFF to
switch to operating mode. The removal of the adhesive
that protects the smoke exit hole of the smoke capsule is
optional, if it is removed the smoke emission starts silently,
otherwise the capsule is better protected against humidity
and the delivery of the smoke will start with a light "bang",
like a shot of a lightning gun.
NO UNWANTED TRIGGER
NUBI 4.0 PREVENTS UNDESIRABLE SMOKE
EMISSIONS ON THE FIRST POWER-ON, DUE TO
WIRING ERRORS. IN ADDITION IT ALLOWS TO
PERFORM FUNCTIONAL TESTS WITHOUT
ACTIVATING THE SMOKE CAPSULE.
In the first 30 minutes after supplying power, NUBI enters a
special
safety operating mode
. During this period the
capsule triggering is preceded by a
warning signal
, the
buzzer emits an intermittent sound for 120 seconds and
the red LED flashes. To stop smoke activation, simply do
one of the following:
•
Place SW7 ON, even for a moment
•
Disarm the alarm (input SI) when the alarm was
caused by the ALL-IN input and/or the infrared
sensor.
•
Give a new impulse to the CSI input when the
alarm was caused by a previous impulse on this
input.
•
Remove the power to the device.
If this warning procedure is not interrupted, smoke will be
delivered at the end of the 120 seconds.
Each time the
warning signal
is triggered, the 30 minute
timer is regenerated to allow for another 30 minutes of
safety operating mode
.
MAINTENANCE
We recommend replacing the smoke capsule every 5
years using only the original replacement.
SMOKE CAPSULE REPLACEMENT
When a smoke capsule is exhausted, it must be replaced
with a new one, using only original spare parts.
Remove the power supply or the battery and wait at
least 10 seconds before replacing the smoke
capsule.
WARRANTY
SMARTEK s.r.l. guarantees its products against all
manufacturing defects for a period of 30 months from the
date of the production batch indicated on the label.
RECOMMENDATIONS
Before leaving, ventilate the rooms thoroughly after the
smoke has been delivered.
ADVANCED WIRING
When the inputs are driven in voltage, it is recommended
to respect the following thresholds:
12VDC
Battery 3,6V
Min V
Max V
Min V
Max V
Level 0
GND
2,0V
GND
0,5V
Level 1
8,0V
+VCC
1,9V
+Vbatt
When only one alarm output is available from the alarm
control unit but not the system status, it is possible to drive
the
SI
and
ALL-IN
inputs in parallel using this output,
therefore NUBI 4.0 will deliver smoke when it detects a
movement with the embedded infrared sensor, but only
while the alarm output remains active. Caution, if the
control panel output also become active with the tamper
alarm, NUBI 4.0 will be activated also for this condition.
TECHNICAL SPECIFICATIONS
Power supply (12VDC
models)
From 10 to 15VDC
< 0,1mA
Power supply (Battery
models)
3,6V lithium battery AA
such as SAFT LS14500
Autonomy about 10 years
Size
12cm x 17cm x 14cm
Saturable volume
100m
3
Weight
760g
Smoke average delivery time
25sec
Operating temperature
From -20°C to +70°C
Maximum relative humidity
90%
Inputs
3
Outputs
3