Longo programmable controller LPC-2.DD4
4 OPERATION
Module parameters can be read or written via Smarteh IDE software.
4.1 Parameters
If parameter is set to logical “1”, is considered to be active, enabled or set. If parameter has logical
value “0”, is considered to be inactive, disabled or cleared.
Parameter can be an output, input, status or setting. Output and input parameters correspond to
the physical output and input pins of the module. Status parameters are used for additional
information from the module, where setting parameters are used to select different settings on the
module.
Output:
L1/Q1 – Dimmer output
[OUT1]
:
Output setting
Type: UINT
If
PSINtype
i
s “0”:
Raw to engineering data:
500 .. 10000 5.00 .. 100.00 %
→
1 .. 499 Output off with fade-out effect
→
0 Immediate output off
→
i
s “1”:
Raw to engineering data:
2 .. 10000 0.02 .. 100.00 %
→
1 Output off with fade-out effect
→
0 Immediate output off
→
L2/Q2 – Dimmer output
[OUT2]
:
Output setting
Type: UINT
If
PSINtype
i
s “0”:
Raw to engineering data:
500 .. 10000 5.00 .. 100.00 %
→
1 .. 499 Output off with fade-out effect
→
0 Immediate output off
→
i
s “1”:
Raw to engineering data:
2 .. 10000 0.02 .. 100.00 %
→
1 Output off with fade-out effect
→
0 Immediate output off
→
L3/Q3 – Dimmer output
[OUT3]
:
Output setting
Type: UINT
If
PSINtype
i
s “0”:
Raw to engineering data:
500 .. 10000 5.00 .. 100.00 %
→
1 .. 499 Output off with fade-out effect
→
0 Immediate output off
→
4