background image

OUTPUT  2

OUTPUT  1

INPUT 1 INPUT 2 

EXPAN 1

EXPAN 2

A

B

+3V

SET

RST

N/O

COM

N/C

N/O

COM

N/C

+3V

SET

RST

A

B

FAULT

ACTIVE

RLY 1

RLY 2

 7  Input wiring

 8  Output wiring

Operating temperature   

-10 to +55 °C 

 

Storage temperature 

 

With batteries 

 

 

-10 to +30 °C

Without batteries

  

 

-10 to +55 °C

Humidity 

 

 

0 to 95% noncondensing

Location 

   Type A: for indoor use

Supply   

 

 

3 x ER14505M 3.6 V lithium thionyl chloride

    batteries 

(Fanso 

or 

Titus)

CAUTION! 

Operating voltage 

 

2.7 to 3.65 VDC

Operating frequency 

 

868 MHz

Output transmitter power  

14 dBm / 25 mW

Signalling protocol 

 

X5

Dimensions (W x H x D)

 

 

150 x 200 x 55mm

Manufacturer  

EMS Ltd. Technology House, Herne Bay, Kent, CT6 8JZ.  

   United 

Kingdom

Year of manufacture 

See devices serial number label 

Certification

Certification body

CPR certificate DoP 

0359-CPR-00269

Approved to 

 

EN54-13:2005. Fire detection and fire alarm systems.    

 

 

 

Part 13: compatibility assessment of system    

 

   components.

 

 

 

EN54-18:2005. Fire detection and fire alarm systems.    

 

 

 

Part 18: input/output devices.

 

 

 

EN54-25:2008. Incorporating corrigenda september    

 

 

 

2010 and march 2012. Fire detection and fire alarm    

 

 

 

systems. Part 25: components using radio links.

European Union    

EMS declares that the radio equipment type SmartCell 

directives   Dual Input / Output Device is in compliance with  

 

 

 

 

Directive 2014/53/EU. The full text of the EU   

 

 

 

 

declaration of conformity is available at the following  

   internet 

 

address: 

www.mysmartcell.co.uk

   2012/19/EC (WEEE directive): Products marked with    

 

 

 

this symbol cannot be disposed of as unsorted  

 

 

 

 

municipal waste in the European Union. For proper    

 

 

 

recycling, return this product to your local supplier    

 

 

 

upon purchase of equivalent new equipment, or  

 

 

 

 

dispose of it at designated collection points. For more  

   information 

see 

www.recyclethis.info

 

 

 

Dispose of your batteries in an environmentally  

 

 

 

 

friendly manner according to your local regulations.

19

Two resistor monitored inputs are 

available. 

Both inputs monitor; normal, 

alarm, open circuit and closed 

circuit conditions.

Each input is factory fitted with an 

end of line 20 kΩ resistor.

To connect inputs to external 

devices, wire as shown, using the 

resistors provided.

Minimum input detection time is 2 

seconds.

If an input is not being used, leave 

the 20 kΩ resistor as factory fitted.

Two outputs are available. 

Both outputs are voltage free, 

with a maximum switching 

capacity of  30 V at 1 A.

This product contains relays which when subjected to severe mechanical shock 

may cause momentary transitions from the currently active state. The 

transitions will be less than 1 second and any equipment connected must not 

respond to such momentary changes of the relay. This product should be fixed 

to a stable and secure structure that is not subject to severe mechanical shock.

0359

OUTPUT 1 OUTPUT 2

N/O CO

M

N/C

N/O CO

M

N/C

20k 4k7

C

N/O

EOL resistor 

configuration 

Remote monitored device

A

B

INPUT 1

A

B

INPUT 2

Note: max cable 

length of 10 m

20kΩ

!

9  LED operation

10  Completing the installation

Output 1

LED

Output 2

LED

Input 2 

LEDs

Input 1 

LEDs

The front lid must now be re fitted to the device and all four fixing screws 

tightened to fully reassemble the unit.

The device has six indication LEDs. They operate as follows:

Input fault: 

 

YELLOW LED ON           

Input active: 

 

RED LED ON            

Output active:  

RED LED ON            

Application label

This can be utilised to 

identify connected 

circuits as per the 

above example

Status LED location 

This status LED is 

multi functional.

 

See 

programming manual 

(TSD155) 

for full  

details of operation

WARNING. DO NOT CONNECT TO MAINS.

 Specification

 Regulatory information

STATUS

DUAL INPUT/OUTPUT DEVICE

LOG ON POINT

Input 1: BEAM DETECTION
Input 2: GAS DETECTION
Output 1: FAN SHUT OFF
Output 2: GAS SHUT OFF

©2020 EMS Ltd.  All rights reserved.                                                                                                       Page 1 of 2 

 

TSD089-0001-99 (Issue 1) 12/05/2020 AJM                                                                                                                                                                                                                                                        

This is a life safety product. Only use manufacturer approved battery types. 

Failure to do so may result in damage to the product.

DO NOT mix batteries of different type or age.

When replacing batteries; remove all old batteries before fitting replacements. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Отзывы: