background image

0017A3

(B)

(A)

Operating temperature   

-10 to +55 °C

Storage temperature

With batteries 

 

 

-10 to +30 °C

Without batteries  

 

-10 to +55 °C

Humidity 

 

 

0 to 95% noncondensing

Location  

 

 

Type A: for indoor use

IP rating 

   IP21C

Supply   

 

 

3 x ER14505M 3.6 V lithium thionyl chloride

    batteries 

(Fanso 

or 

Titus)

CAUTION! 

 

Operating voltage 

 

2.7 to 3.65 VDC

Current consumption 

 

0.32 A max.

Power consumption 

 

0.8 W max.

Operating frequency 

 

868 MHz

Output transmitter power  

14 dBm / 25 mW

Signalling protocol 

 

X5

Flash Rate  

 

 

0.5 Hz (1 flash, every 2 seconds)

Beacon 

coverage 

  C-3-12

Sounder output   

 

92 dB(A) at 1 m max.

For full sounder output information, refer to the Sounder Data doc (MK103).

Dimensions (Ø x D) 

 

110 x 79 mm

Approved to

  

EN54-3:2001. Incorporating amendments nos. 1 and 2.  

 

 

 

Fire detection and fire alarm systems.

 

 

 

Part 3: fire alarm devices - sounders.

                  

 

 

 

EN54-13:2005. Fire detection and fire alarm systems.    

 

 

 

Part 13: compatibility assessment of system    

 

   components.
 

 

 

EN54-23:2010. Fire detection and fire alarm systems.    

 

 

 

Part 23: fire alarm devices. Visual alarm devices. 

 

 

 

EN54-25:2008. Incorporating corrigenda september    

 

 

 

2010 and march 2012. Fire detection and fire alarm    

   systems. 

 

 

 

Part 25: components using radio links.

European Union    

EMS declares that the radio equipment type

directives

  

SmartCell Sounder & Ceiling Beacon is in compliance  

 

 

 

with Directive 2014/53/EU. The full text of the EU  

 

 

 

 

declaration of conformity is available at the following  

   internet 

 

address: 

www.mysmartcell.co.uk

   2012/19/EC (WEEE directive): Products marked with    

 

 

 

this symbol cannot be disposed of as unsorted  

 

 

 

 

municipal waste in the European Union. For proper    

 

 

 

recycling, return this product to your local supplier    

 

 

 

upon purchase of equivalent new equipment, or  

 

 

 

 

dispose of it at designated collection points. For more  

   information 

see 

www.recyclethis.info

 

 

 

Dispose of your batteries in an environmentally  

 

 

 

 

friendly manner according to your local regulations.

Manufacturer  

EMS Ltd. Technology House, Herne Bay, Kent, CT6 8JZ.  

   United 

Kingdom

Year of manufacture 

See devices serial number label 

Certification
Certification body  
CPR certificate DoP 

0359-CPR-00428

19

0359

Specification

Reassemble the device as shown below.

8  Completing the installation

Device unlocking

If the device has been locked, an 

Allen key will be required for 

unlocking.

Depress the locking mechanism, 

by inserting the Allen key, or 

similar, into the device’s cavity 

and pushing (A).

Simultaneously twist the device 

anti-clockwise to release (B).

 

      IMPORTANT

!

The device should be tested upon installation, in accordance with local 

requirements.

Testing should only be carried out by a fully trained competent person.

Regulatory information

7  Optional device locking

The device includes an optional locking mechanism.

Remove the thin section of plastic shown below.

Once locked, the Allen key will be required

to unlock the device.

©2019 EMS Ltd.  All rights reserved.                                                                                                       Page 2 of 2 

 

TSD108-0001-99 (Issue 1) 26/09/2019 AJM

This is a life safety product. Only use manufacturer approved battery types. 

Failure to do so may result in damage to the product.

DO NOT mix batteries of different type or age.

When replacing batteries; remove all old batteries before fitting replacements. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Отзывы: