0017A3
(B)
(A)
Operating temperature
-10 to +55 °C
Storage temperature
With batteries
-10 to +30 °C
Without batteries
-10 to +55 °C
Humidity
0 to 95% noncondensing
Location
Type A: for indoor use
IP rating
IP21C
Supply
3 x ER14505M 3.6 V lithium thionyl chloride
batteries
(Fanso
or
Titus)
CAUTION!
Operating voltage
2.7 to 3.65 VDC
Current consumption
0.32 A max.
Power consumption
0.8 W max.
Operating frequency
868 MHz
Output transmitter power
14 dBm / 25 mW
Signalling protocol
X5
Flash Rate
0.5 Hz (1 flash, every 2 seconds)
Beacon
coverage
C-3-12
Sounder output
92 dB(A) at 1 m max.
For full sounder output information, refer to the Sounder Data doc (MK103).
Dimensions (Ø x D)
110 x 79 mm
Approved to
EN54-3:2001. Incorporating amendments nos. 1 and 2.
Fire detection and fire alarm systems.
Part 3: fire alarm devices - sounders.
EN54-13:2005. Fire detection and fire alarm systems.
Part 13: compatibility assessment of system
components.
EN54-23:2010. Fire detection and fire alarm systems.
Part 23: fire alarm devices. Visual alarm devices.
EN54-25:2008. Incorporating corrigenda september
2010 and march 2012. Fire detection and fire alarm
systems.
Part 25: components using radio links.
European Union
EMS declares that the radio equipment type
directives
SmartCell Sounder & Ceiling Beacon is in compliance
with Directive 2014/53/EU. The full text of the EU
declaration of conformity is available at the following
internet
address:
www.mysmartcell.co.uk
2012/19/EC (WEEE directive): Products marked with
this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper
recycling, return this product to your local supplier
upon purchase of equivalent new equipment, or
dispose of it at designated collection points. For more
information
see
www.recyclethis.info
Dispose of your batteries in an environmentally
friendly manner according to your local regulations.
Manufacturer
EMS Ltd. Technology House, Herne Bay, Kent, CT6 8JZ.
United
Kingdom
Year of manufacture
See devices serial number label
Certification
Certification body
CPR certificate DoP
0359-CPR-00428
19
0359
Specification
Reassemble the device as shown below.
8 Completing the installation
Device unlocking
If the device has been locked, an
Allen key will be required for
unlocking.
Depress the locking mechanism,
by inserting the Allen key, or
similar, into the device’s cavity
and pushing (A).
Simultaneously twist the device
anti-clockwise to release (B).
IMPORTANT
!
The device should be tested upon installation, in accordance with local
requirements.
Testing should only be carried out by a fully trained competent person.
Regulatory information
7 Optional device locking
The device includes an optional locking mechanism.
Remove the thin section of plastic shown below.
Once locked, the Allen key will be required
to unlock the device.
©2019 EMS Ltd. All rights reserved. Page 2 of 2
TSD108-0001-99 (Issue 1) 26/09/2019 AJM
This is a life safety product. Only use manufacturer approved battery types.
Failure to do so may result in damage to the product.
DO NOT mix batteries of different type or age.
When replacing batteries; remove all old batteries before fitting replacements.