Device unlocking
IMPORTANT
9
8 Completing the installation
Reassemble the device as shown below.
!
Remove dust cover before use.
The device should be tested upon installation and in accordance with local
requirements.
Testing should only be carried out by a fully trained competent person.
The manufacturer recommends regular functional testing in accordance with
local codes of practice.
Cleaning and repairs must be undertaken by the manufacturer’s authorised
representative.
Do not open the case to clean inside the detector.
7 Optional device locking
Operating temperature
-10 to +55 °C
Storage temperature
With batteries
-10 to +30 °C
Without batteries
-10 to +55 °C
Humidity
0 to 95% noncondensing
Location
Type A: for indoor use
IP rating
IP21C
Supply
3 x ER14505M 3.6 V lithium thionyl chloride
batteries
(Fanso
or
Titus)
CAUTION!
Operating voltage
2.7 to 3.65 VDC
Current consumption
0.15 A max.
Power consumption
0.38 W max.
Operating frequency
868 MHz
Output transmitter power
14 dBm / 25 mW
Signalling protocol
X5
Detector sensitivity and
Smoke: Normal*†, AVF,
responsivity settings
Heat: 58°c static (A2S)*†, 58c rate of rise (A2R)*,
72°c static (BS)* & 72°c rate of rise (BR)*
* EN54 approved sensitivities † Default dual sensitivities
Sounder output
89 dB(A) at 1 m max.
For full sounder output information, refer to the Sounder Data doc (MK103).
Dimensions (Ø x D)
110 x 58 mm
Specification
Certification
Certification body
CPR DoP
0905
19
EN54-3:2001. Incorporating amendments nos. 1 and 2. Fire
detection and fire alarm systems. Part 3: fire alarm devices -
sounders.
EN54-5:2001. Incorporating Amendment No. 1. Fire detection
and fire alarm systems. Part 5: heat detectors - point
detectors.
EN54-7:2001. Incorporating amendment no. 1. Fire detection
and fire alarm systems. Part 7: smoke detectors - point
detectors using scattered light, transmitted light or ionization.
EN54-13:2005. Fire detection and fire alarm systems.
Part 13: compatibility assessment of system components.
EN54-25:2008. Incorporating corrigenda september 2010 and
march 2012. Fire detection and fire alarm systems. Part 25:
components using radio links.
EMS declares that the radio equipment type SmartCell Dual
Detector With Combined Sounder is in compliance with
Directive 2014/53/EU. The full text of the EU declaration of
conformity is available at the following internet address:
www.mysmartcell.com
2012/19/EC (WEEE directive): Products marked with this
symbol cannot be disposed of as unsorted municipal waste in
the European Union. For proper recycling, return this product
to your local supplier upon purchase of equivalent new
equipment, or dispose of it at designated collection points.
For more information see www.recyclethis.info
Dispose of your batteries in an environmentally friendly
manner according to your local regulations.
European Union
directives
Approved to
Manufacturer
Carrier Manufacturing Polska Sp. Z o.o. Ul. Kolejowa 24.
39-100 Ropczyce, Poland
Year of manufacture See devices serial number label
0359-CPR-00268
Regulatory information
The device includes an optional locking mechanism.
Remove the thin section of plastic shown below.
Once locked, the Allen key will be required
to unlock the device.
If the device has been locked, an
Allen key will be required for
unlocking.
Depress the locking mechanism,
by inserting the Allen key, or
similar, into the device’s cavity
and pushing (A).
Simultaneously twist the device
anti-clockwise to release (B).
©2021 EMS Ltd. All rights reserved. Page 2 of 2
TSD090-0001-99 (Issue 3) 25/08/2021 AJM
This is a life safety product. Only use manufacturer approved battery types.
Failure to do so may result in damage to the product.
DO NOT mix batteries of different type or age.
When replacing batteries; remove all old batteries before fitting replacements.