0017A3
(A)
(B)
Operating temperature
-10 to +55 °C
Storage temperature
With batteries
-10 to +30 °C
Without batteries
-10 to +55 °C
Humidity
0 to 95% noncondensing
Location
Type A: for indoor use
Supply
3 x ER14505M 3.6 V lithium thionyl chloride
batteries
(Fanso
&
Titus)
CAUTION!
Operating voltage
2.7 to 3.65 VDC
Operating frequency
868 MHz
Output transmitter power
14 dBm / 25 mW
Signalling protocol X5
Detector sensitivity and
Smoke: Normal*†, AVF,
responsivity settings
Heat: 58 °c static (A2S)*†, 58 °c rate of rise
(A2R)*, 72 °c static (BS)* & 72 °c rate of rise (BR)*
* EN54 approved sensitivities
†
Default dual sensitivities
Dimensions (Ø x D)
110 x 58 mm
Specification
Manufacturer
Carrier Manufacturing Polska Sp. Z o.o. Ul. Kolejowa 24.
39-100
Ropczyce,
Poland
Year of manufacture
See devices serial number label
Certification
Certification body
CPR DoP
0359-CPR-00265
Approved to
EN54-5:2001. Incorporating amendment no. 1. Fire
detection and fire alarm systems. Part 5: heat detectors
-
point
detectors.
EN54-7:2001. Incorporating amendment no. 1. Fire
detection and fire alarm systems. Part 7: smoke
detectors - point detectors using scattered light,
transmitted light or ionization.
EN54-13:2005. Fire detection and fire alarm systems.
Part 13: compatibility assessment of system
components.
EN54-25:2008. Incorporating corrigenda september
2010 and march 2012. Fire detection and fire alarm
systems. Part 25: components using radio links.
European Union
EMS declares that the radio equipment type SmartCell
directives
Dual Smoke / Heat Detector is in compliance with
Directive 2014/53/EU. The full text of the EU declaration
of conformity is available at the following internet
address:
www.mysmartcell.com
2012/19/EC (WEEE directive): Products marked with
this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper
recycling, return this product to your local supplier
upon purchase of equivalent new equipment, or
dispose of it at designated collection points. For more
information
see
www.recyclethis.info
Dispose of your batteries in an environmentally
friendly manner according to your local regulations.
19
0905
9 Device unlocking
Remove dust cover before use.
The device should be tested upon installation and in accordance with local
requirements.
Testing should only be carried out by a fully trained competent person.
The manufacturer recommends regular functional testing in accordance with
local codes of practice.
Cleaning and repairs must be undertaken by the manufacturer’s authorised
representative.
Do not open the case to clean inside the detector.
IMPORTANT
!
9
8 Completing the installation
Reassemble the device as shown below.
7 Optional device locking
Regulatory information
The device includes an optional locking mechanism.
Remove the thin section of plastic shown below.
Once locked, the Allen key will be required
to unlock the device.
If the device has been locked, an
Allen key will be required for
unlocking.
Depress the locking mechanism,
by inserting the Allen key, or
similar, into the device’s cavity
and pushing (A).
Simultaneously twist the device
anti-clockwise to release (B).
This is a life safety product. Only use manufacturer approved battery types.
Failure to do so may result in damage to the product.
DO NOT mix batteries of different type or age.
When replacing batteries; remove all old batteries before fitting replacements.