SMART Centellis 2000 DC 1.2 Скачать руководство пользователя страница 2

Centellis 2000 DC 1.2 Quick Start Guide

SMART Embedded Computing, 2900 S. Diablo Way, Suite 190, Tempe, Arizona 85282

8 Power up the system

Make sure that the system has been located in a place with room 
temperature for at least 24 hours before powering it up.

Perform the following steps for both power entry modules:

1. Check the LEDs on the front of the module. 

Make sure that the Reverse LED (red) is off and 
that the In LED (green) is on. 

2. Switch on the breaker.

9 Connect to shelf manager

Establish a network connection to the active shelf manager:

1. On the rear of the shelf, plug the network connector in the 

MGMT ETH jack of the MF105 whose yellow ACT LED is lit.

2. Access the shelf manager via its default IP address using telnet 

or SSH, user name and password: root. 

The default IP addresses are as follows:

.

10 Set shelf geographical and 

IP addresses

1. Set the shelf geographical address as required. The default 

shelf geographical address is 0.

2. Change the shelf manager IP-addresses if required. For more 

information, see the 

Centellis 2000 DC 1.2 Installation and Use

 

manual.

3. Define the IP addresses of the node blades. There are no 

predefined IP addresses for the node blades. 

For more information, see the documentation of the respective 
blade.

11 Boot the node blades

Boot the node blades via the network connection. For details on the 
boot process, see the documentation of the respective blade.

12 Check for firmware 

upgrades

Before putting the system into operation, SMART Embedded 
Computing recommends to check for firmware upgrades. 

Install the latest firmware upgrades.

For more information, see the 

Centellis 2000 DC 1.2 Installation and 

Use 

manual.

ATCA-MF105

IP Address

Left ATCA-MF105

192.168.0.8

Right ATCA-MF105

192.168.0.9

Active ATCA-MF105

192.168.0.171

Standby ATCA-MF105

192.168.0.181

© 2020 SMART Embedded Computing™, Inc. All rights reserved. The stylized “S” and 
“SMART” is a registered trademark of SMART Modular Technologies, Inc. and “SMART 
Embedded Computing” and the SMART Embedded Computing logo are trademarks of 
SMART Modular Technologies, Inc. All other names and logos referred to are trade names, 
trademarks, or registered trademarks of their respective owners. These materials are 
provided by SMART Embedded Computing as a service to its customers and may be used 
for informational purposes only. For full legal terms and conditions, visit

 

www.smartembedded.com/ec/legal.

Get More Information

For more information on this product, see the 

Centellis 

2000 DC 1.2 Installation and Use 

manual and other 

related technical documentation, which can be found by 
using the Documentation Search at 

https://www.smartembedded.com/ec/support/

.

Technical Assistance

For technical assistance or to report product damage or shortages, 
contact your local SMART Embedded Computing sales 
representative or visit 

https://www.smartembedded.com/ec/support/.