The function of checking the data for compliance with the
specified conditions allows you to automate the operation of a
controlled output or receive notifications.
- In total, you can configure up to 6 conditions.
- Conditions do not have the opposite effect, i.e. if the condition
is met and the relay turns on, then the relay will not turn off for
the same condition. To turn on/off a relay, you always need two
conditions.
- Conditions are checked from top to bottom, from 1st to 6th. The
relay takes on the state according to the last fulfilled condition.
- During the check of the switching conditions, the relay does not
occur, i.e. the relay turns on or off only after all conditions have been
checked.
- Note: first, set the condition common to all others, for example,
switch off the relay by condition, which is always fulfilled "1> 0"
- To exclude false alarms, set the "Filter up to [sec]", the condition
will be fulfilled only if the value is in the specified range for more than
the specified number of seconds. Random spikes and fluctuations
will be filtered out.
- The condition check can be limited in time. If you activate a time
interval, the condition will be executed only within the specified
time.
- Set the "Delay after [sec]" relay switching, during which the relay
will not be switched regardless of the conditions. The minimum
time is 60 seconds.
Setting conditions is available on the device WEB interface in the
"Conditions" section.