Configuration
3.21
Calibrating Using Local Adjustment
In order to follow the example bellow the Display Transducer block should be configured to show
these parameters: CAL_POINT_HI (mnemonic UPPER), CAL_POINT_LO (mnemonic LOWER)
and TAG (mnemonic TAG).
The transmitter has two holes for magnetic switches, located under the identification plate. These
magnetic switches are activated by one magnetic tool.
This magnetic tool enables adjustment of the most important parameters of the blocks. It also
enables pre-configuration of the communication.
The jumper w1 on top of the main circuit board must be in place and the transmitter must be fitted
with the digital display for access to the local adjustment. Without the display the local adjustment is
not possible.
In order to enter the local adjustment mode, place the magnetic tool in orifice “Z” until flag “MD”
lights up in the display. Removes magnetic tool from “Z” and place it in orifice “S”. Remove and
reinsert the magnetic tool in “S” until the message “LOC ADJ” is displayed.
The message will be displayed during approximately 5 seconds after the user removes the magnetic
tool from “S”. By placing the magnetic tool in “Z” the user will be able to access the local
adjustment/monitoring tree.
The jumper W1 on top of the main circuit board must be in place and the transmitter must be fitted
with digital display for access to the local adjustment. Without display, the local adjustment is not
possible.
Figure 3.16 - Local Adjustment
Table 3.4 shows the actions on the
Z
and
S
holes on the
DT302
when Local Adjustment is enabled.
HOLE
ACTION
Z
Initializes and rotates through the available functions.
S
Selects the function shown in the display.
Table 3.4 - Purpose of the holes on the Housing
J1 Jumper Connections
If J1 (see figure 3.21) is connected to ON, then simulation mode in the AI block is enabled.
Содержание DT302
Страница 7: ...Kpuvcnncvkqp Hnqyejctv XKK Kpuvcnncvkqp Hnqyejctv...
Страница 8: ...FV524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK...
Страница 34: ...DT302 Operation Maintenance and Instructions Manual 2 4...
Страница 64: ...DT302 Operation Maintenance and Instructions Manual 4 6 Figure 4 3 DT302 Exploded View Sanitary Model...
Страница 65: ...Maintenance Procedures 4 7 Figure 4 4 DT302 Exploded View Industrial Model...
Страница 68: ...DT302 Operation Maintenance and Instructions Manual 4 10...
Страница 79: ...Egtvkhkecvkqpu Kphqtocvkqp C07 EXAM and NEMKO...
Страница 80: ...FV524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C08 CEPEL...
Страница 81: ...Egtvkhkecvkqpu Kphqtocvkqp C09 Control Drawing Factory Mutual FM...
Страница 82: ...FV524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0...
Страница 84: ...DT302 Operation Maintenance and Instructions Manual B 2...