SMAR DF17 Скачать руководство пользователя страница 4

DF16 / DF17 – INSTALLATION MANUAL

2

Internal Power

Provided by the IMB bus

5 Vdc @ 50 mA Maximum

Total Maximum Dissipation

0.25 W

Indicator of source

Green LED

Inputs

ON State Level (True Logic)

100-140 Vac (DF16)

200-264 Vac (DF17)

OFF State Level (False Logic)

0-30 Vac (DF16)

0-50 Vac (DF17)

Typical Input current

10 mA

Status display

Yellow LED

Switching Information

Minimum Voltage ( 0 to 1)

100 Vac (DF16), 45 to 60 Hz

200 Vac (DF17), 45 to 60 Hz

Maximum Voltage (1 to 0)

30 Vac  (DF16), 45 to 60 Hz

50 Vac (DF17), 45 to 60 Hz

Typical Hysteresis

70 Vac  (DF16)

150 Vac  (DF17)

Time from 0 to 1

5 ms

Time from 1 to 0

42 ms

Dimensions and Weight

Dimensions (WxHxD)

39.9x137.0x141.5 mm ; (1.57x5.39x5.57 in)

Weight

0.285 kg

Wire

One wire

14 AWG (2 mm

2

)

Two wires

20 AWG (0.5 mm

2

)

Отзывы: