Configuration
3.21
Unit_Diag_Bit(93) = "DI 11 and/or DI 12 Block: Out of Service"
Unit_Diag_Bit(94) = "DI 13 and/or DI 14 v: Out of Service"
Unit_Diag_Bit(95) = "DI 15 and/or DI 16 Block: Out of Service"
Unit_Diag_Bit(96) = "DO 1 Block: Out of Service"
Unit_Diag_Bit(97) = "DO 2 Block: Out of Service"
Unit_Diag_Bit(98) = "DO 3 Block: Out of Service"
Unit_Diag_Bit(99) = "DO 4 Block: Out of Service"
Unit_Diag_Bit(100) = "DO 5 Block: Out of Service"
Unit_Diag_Bit(101) = "DO 6 Block: Out of Service"
Unit_Diag_Bit(102) = "DO 7 Block: Out of Service"
Unit_Diag_Bit(103) = "DO 8 Block: Out of Service"
Addressing the DC303
1. During the initialization procedure (ie, when powering the
DC303
), if the simulate jumper is
configured to "on", the physical address is shown on the outputs and this way, the user can
verify the node address on the outputs 1-7, through the LEDs. When the led is on, the address
bit represents “1”. Output 1 is the least significant bit and the output 7 represents the most
significant bit.
2. The output 8 is used to indicates the Identifier_Number_Selector and
when is “on” (on state)
indicates
“Manufacturer Specific " and “off” (off state), indicates Profile Specific ".
3. When in "Manufacturer Specific", the Identifier Number is 0x0dca.
Once the
Identifier_Number_Selector is changed from " Profile Specific " to "Manufacturer Specific" or
vice-versa, you must wait 5 seconds while it is saved and the turn off the
DC303
and then the
identifier is updated in the level of communication. If the equipment is in "Profile Specific" and
using the GSD file Identifier Number equals 0x0dca, the acyclic communication will work well
with tools based on EDDL, FDT/DTM, but no cyclic communication with the Profibus-DP
master will get success.
ATTENTION
If necessary to execute a reset procedure or a power down and then a power up procedure, if the simulate
jumper is on, please, disconnect the outputs since the
DC303
will activate the outputs according to the
physical address.
Figure 3.15- Simulate Jumper - DC303