English – Version 1.0 – April 2020
Smappee Energy
Installation manual
Страница 1: ...English Version 1 0 April 2020 Smappee Energy Installation manual...
Страница 2: ...instructions 3 2 How to install 5 3 Physical installation 6 4 Cloud connection and setup 11 5 Validation of the installation 12 6 Three phase voltage and current mapping 13 Addendum 1 Colour code expl...
Страница 3: ...ric shock fire or personal injury Use this product only for its intended purpose Use the product indoors only Do not open the equipment or touch any of its electronic circuitry Do not attempt to open...
Страница 4: ...tly in force The device must be installed in accordance with the instructions given in this manual Failure to observe the instructions for installing this unit may compromise the device s intrinsic pr...
Страница 5: ...cal installation The physical installation of all the Smappee Energy components Cloud connection and setup The creation of a location its properties and the loads to be measured 1 Validation of the in...
Страница 6: ...ion and production E g Solar production Three Phase 3P N 3 400 V and 3P 3 230 V total consumption Steps Power off the installation and open the fuse box Connect the current transformers CTs according...
Страница 7: ...atible with 2 4 GHz Wi Fi networks Make sure the Wi Fi network is online when powering on the Smappee monitor The arrow indicated on the CT K L must point in the direction of the current flow Consumpt...
Страница 8: ...ram 1P 1 230 V Brown L1 Blue Neutral Connect the CTs to the Smappee Energy Input 1 Consumption Input 2 Solar Input 3 Do not use Use a digital multimeter to determine the phase wire of the solar invert...
Страница 9: ...L1 Black L2 Grey L3 Blue Neutral WARNING For a three phase installation it is mandatory to setup the voltage and current mapping in the Expert Portal see next pages Incorrect line voltage and current...
Страница 10: ...Brown L1 Black L2 Grey L3 WARNING For a three phase installation it is mandatory to setup the voltage and current mapping in the Expert Portal see next pages Incorrect line voltage and current mappin...
Страница 11: ...step is creating a location and defining the measured loads and their properties Log in to the Smappee App with the corresponding Smappee username or create a new account Create a new location Follow...
Страница 12: ...eal time values of the measured loads You can access these real time values with the mobile app The Smappee App reports real time active power values Consumption is displayed in the yellow bubble Prod...
Страница 13: ...ases E g turn on the lights an electric heater an electric oven a coffee machine a hair dryer Uncheck the Auto Detection checkbox Select each of the 6 options in the Phase to input mapping and click o...
Страница 14: ...ng seems to be incorrect Continue to find the correct configuration Absolute power value is correct Three active power values are negative All Cos Fi are higher than 80 This phase mapping seems to be...
Страница 15: ...erwise the changes to the configuration will not be saved Validate the configuration Refresh press F5 the webpage and log in again to the Expert Portal to see if all changes are saved and the configur...
Страница 16: ...ue Flashing The monitor is ready to be connected to the local Wi Fi network Red Steady The monitor has no connection to the internet during startup Connection issue Red Flashing The monitor had a work...
Страница 17: ...g installation SSID must NOT contain the following characters Allowed special characters for the Wi Fi password MAC filtering must not be active on the router Your firewall should allow Smappee to cre...